surance or local codes require, go to a "lockout” mode. Lockout will require manual reset of the flame safeguard.
4.After completing this test, turn off the boiler and reconnect the wire to the main gas valve. Replace the control panel faceplate.
4.4.2 Test of Low Water Cutoff
The boiler is furnished with a
1.Make sure the boiler is off.
2.Turn the system pump off, stopping water flow in the system. Do not shut the pump off while the boiler is operating.
3.Turn the boiler back on. It should not operate, and a red indicator for "Low Water" or "Water Flow" should be illuminated.
Perform appropriate tests on any external
4.4.3 Test of High-Limit Control
The boiler is furnished with a
1.With the main burner operating, turn down the temperature setting on the
This check should also be made for the "Operating Temperature" control. (The green "Heat" indica- tor will go out.) (See the “Installation and Owner’s Manual,” page 8 for
2.Readjust thermostats to desired operating tem- perature and set
4.4.4Test of Gas Pressure Switch
Reset
Figure
The boiler is furnished with a low gas pressure switch.
1.Slowly close the manual shutoff valve (on the natural gas supply) while the burner is operating. The low gas pressure switch should shut down the main burner before combustion problems are en- countered. When the gas pressure switch opens, the "Low Gas" or "Gas Press" indicator will illu- minate.
2.Reopen the manual shutoff valve. The "Low Gas" or "Gas Press" indicator should remain on until the low gas pressure switch is reset.