Gemini™
Gas Pressure Adjustment
Test of Motorized Gas Valves
4.2GAS PIPING
Before making the gas
Gas train connection sizes are shown in the Gas Train Connection table on the previous page for the different models available.
The boiler shall be installed such that the gas ignition system components are protected from water (drip- ping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replace- ment, etc.).
The two gas pressure regulators supplied with the boiler are set during a factory
The gas train components are designed to handle a maximum inlet pressure of 14 inches W.C.(1/2 psig). If the available gas pressure exceeds 14 inches W.C. on either the natural gas or propane supply a suitable intermediate gas pressure regulator of the "lock up" type must be provided to reduce the pressure to less than 14 inches W.C. All boilers are designed to oper- ate at rated input with a minimum inlet pressure of 6 inches W.C. with natural gas, 6 inches W.C. with LP gas.
- 6 -
natural gas supply
remote gas shutoff | union | |
(not supplied) |
| |
drip leg | shutoff | |
(on boiler) | ||
| ||
propane | shutoff | |
supply | ||
(on boiler) | ||
| ||
remote gas shutoff | union | |
(not supplied) |
| |
drip leg |
|
Figure
(Refer to table above for connection sizes.)
Install a sediment trap (drip leg) and a union connec- tion ahead of the primary manual shutoff valves on the boiler as shown in the figure above.
All gas piping must be installed in accordance with National Fuel Gas Code, ANSI Z223.1, latest edition, and any other local codes which may apply; in Canada gas piping must be installed in accordance with CAN- B 149.
General Warning
Warning! All threaded connections must be made us- ing a pipe compound that is resistant to the action of liquefied petroleum gases. Do not use Teflon tape on gas line threads.
The boiler and all gas piping connections must be pressure tested and must be checked for leaks before being placed into service. Test with compressed air or gas if possible.
The boiler must be disconnected at both boiler manual