BURNER SETUP & BOILER OPERATION
E.CLEAN THE BOILER (STEAM BOILERS ONLY)
1.Clean the boiler within one week after initial
2.Boiler must be cleaned to remove any accumulation of oil, grease, sludge, etc. in the system. These substances can cause foaming and surging of boiler water, producing an unstable water line and water carryover to system.
Cleaning the boiler requires the use
WARNING of very hot water and corrosive chemicals. Use care when handling to prevent injury.
3.Connect a skim valve off the
4.Provide a means of supplying continuous fresh water to the boiler for the cleaning process.
5.Use common washing soda, such as Arm and Hammer Super Washing Soda. Mix 1/2 pound of soda with water in a 10 quart pail. Pour the mixture into the boiler through the safety relief valve tapping.
6.Open the skim valve. Fill boiler until water begins to flow out of the valve.
Do not leave boiler unattended while CAUTION firing burner. Operating boiler with
water below minimum permissible water level may fracture sections.
7.Turn on burner. Allow boiler water to heat up to just below steaming (180 - 200°F). Do not allow boiler to steam; steaming mixes up contaminants instead of floating them at surface.
8.Open
Do not allow
water may fracture sections.
9.Continue skimming boiler until water flowing from skim tapping flows clear. This will take some time, possibly several hours for a dirty system.
10.Turn off burner, close
11.Drain boiler completely. Refill and drain one or two times to wash out all washing soda.
12.Remove skim valve and piping. Install
If gauge glass becomes dirty more NOTICE contaminants have worked loose in
system. Repeat cleaning and skimming process as needed to clean system.
14