Table 5.1: Beckett Burner Specifications

BURNER SETUP & BOILER OPERATION

Table 5.1: Beckett Burner Specifications

BECKETT BURNER SPECIFICATIONS

Boiler

Burner

Burner

Static

Nozzle Size

Pump

Start-up Settings

Head

Model No.

Model No.

Head

Plate

Pressure

Air Shutter

Air Band

Setting

 

 

 

 

 

 

 

 

 

 

 

 

WBV-03-085

AFG-F3¹

F3

3-3/8"

0.75

80° B HAGO³

140 PSI

6.0

1

N/A

 

 

 

 

 

 

 

 

 

 

WBV-03-105

AFG-F4

F4

3-3/8"

0.90

80° B HAGO

140 PSI

6.0

0

N/A

 

 

 

 

 

 

 

 

 

WBV-04-095

AFG-F4

F4

3-3/8"

0.85 80° B DEL4

140 PSI

6.0

0

N/A

 

 

 

 

 

 

 

 

 

 

WBV-04-125

AFG-F4

F4

3-3/8"

1.10

80° B HAGO³

140 PSI

5.0

2

N/A

 

 

 

 

 

 

 

 

 

 

WBV-04-150

AFG-F6

F6

2-3/4"

1.25

80° B HAGO

140 PSI

8.0

1

N/A

 

 

 

 

 

 

 

 

 

 

WV-05-175

AFG-MV1

V-1

-

1.50

60° B HAGO³

140 PSI

10.0

3

3

 

 

 

 

 

 

 

 

 

 

WV-05-195

AFG-MV1

V-1

-

1.65

60° B HAGO

140 PSI

10.0

9

3

 

 

 

 

 

 

 

 

 

 

BECKETT NX BURNER SPECIFICATIONS

Boiler Model No.

Burner Model

Nozzle Size

Pump Pressure

Start Up Head/Air

 

 

 

 

 

WBV-03-085

NX70LB

0.65 x 60° W DEL³

170

1.5

 

 

 

 

 

WBV-03-105

NX70LB

0.85 x 60° B HAGO

170

2.5

 

 

 

 

 

WBV-04-095

NX70LB

0.75 x 60° W DEL4

170

2.0

WBV-04-125

NX70LD

1.10 x 60° W DEL³

140

1.0

 

 

 

 

 

WBV-04-150

NX70LD

1.25 x 60° W DEL

140

2.0

 

 

 

 

 

Note: Burner used to fire the WBV-03-.085 and 1.05 rate is also required to fire the WBV-04-.95 rate with nozzle indicated in above chart.

Table 5.2: Carlin Burner Specifications (with 98022 PSC motor)

CARLIN BURNER SPECIFICATIONS (WITH 98022 PSC MOTOR)

Boiler

Burner

Head Bar

Nozzle Size

Pump Pressure

Start-up Settings

Model No.

Model No.

Air Shutter

Air Band

 

 

 

 

 

 

 

 

 

 

 

WBV-03-085

EZ-1HP

0.60 - 0.65

0.65 70° A DEL³

150 PSI

Blank

0.60

 

 

 

 

 

 

 

 

WBV-03-105

EZ-1HP

0.85 - 1.00

0.85

70° A DEL

150 PSI

Blank

0.65

 

 

 

 

 

 

 

 

WBV-04-095

EZ-1HP

0.75

0.75

70° A DEL4

150 PSI

Blank

0.60

 

 

 

 

 

 

 

WBV-04-125

EZ-1HP

0.85 - 1.00

1.00 70° A DEL³

150 PSI

Blank

0.85

 

 

 

 

 

 

 

 

WBV-04-150

EZ-1HP

1.10 - 1.25

1.25

60° B DEL

150 PSI

Blank

1.00

 

 

 

 

 

 

 

WV-05-175

99FRD

N/A

1.50 60° B HAGO³

150 PSI

Open

10% open

 

 

 

 

 

 

 

WV-05-195

99FRD

N/A

1.65 60° B HAGO

150 PSI

Open

45% open

 

 

 

 

 

 

 

 

Table 5.3: Riello Burner Specifications

RIELLO BURNER SPECIFICATIONS

Boiler

Burner

Burner Series

Nozzle Size²

Pump Pressure

Start-Up Settings

Model No.

Model No.

Turbulator

Air Damper

 

 

 

 

 

 

 

 

 

 

 

WBV-03-060

F3

Series 40

0.50 90° B

145 PSI

0.0

2.9

 

 

 

 

 

 

 

WBV-03-085

F5

Series 40

0.65 60° W³

170 PSI

1.0

2.45

 

 

 

 

 

 

 

 

WBV-03-105

F5

Series 40

0.85

60° W

165 PSI

2.5

2.8

 

 

 

 

 

 

 

 

WBV-04-095

F5

Series 40

0.75

80° B4

160 PSI

0.5

2.25

 

 

 

 

 

 

 

WBV-04-125

F5

Series 40

1.00 60° W³

155 PSI

2.5

3.4

 

 

 

 

 

 

 

 

WBV-04-140

F5

Series 40

1.10

60° W

160 PSI

4.0

4.2

 

 

 

 

 

 

 

WV-05-175

F10

Series 40

1.35 60° B³

165 PSI

2.0

2.5

 

 

 

 

 

 

 

WV-05-195

F10

Series 40

1.50 60° B

170 PSI

2.5

2.8

 

 

 

 

 

 

 

 

Factory Installed Nozzles (Packaged Boilers or Burner Cartons) are indicated in Boldface.

1Requires Low Firing Rate Baffle

2Delavan Recommended

3Shipped Loose with Packaged Boiler or Burner Carton

4Not included with Packaged Boiler or Burner Carton