Calibrating I/O

Calibrating I/O

All I/O channels are factory calibrated and should not need recalibration during initial use. However should calibration be required, you can recalibrate in DeviceManager or WebManager. In DeviceManager, you calibrate the I/O channel(s) by selecting Tools, I/O Channels, Calibrate. In WebManager, you calibrate the I/O channel(s) by selecting I/O Channels, Calibrate.

Calibrating Analog Input

To calibrate an Analog input channel, read the section that applies to the type of input you are calibrating. Note that calibration will be done for the active channel configuration; for example, if Channel A1 is set to voltage, you cannot calibrate it for current. The voltage range configured for this channel will also dictate what is being calibrated. For example, if this channel is configured for a range of +/-10V, calibrating this channel will calibrate all channels which are configured for +/-10V. During the calibration process, you will be asked to apply the minimum and maximum configured range value to the channel; for example, to calibrate for voltage +/- 10V, you will be prompted to first apply -10V and then +10V to the channel.

Also, you cannot actively calibrate disabled channels (although, for Voltage, if you enable the channel and then set it for a range that has already been calibrated for another channel, it will also be calibrated).

Calibrating Voltage

When calibrating the IOLAN Analog input for voltage, you will need a calibration meter that is better than .1% volts precision. When you calibrate one channel, all voltage channels are automatically calibrated for that range; if another channel is set for a different range, you will need to calibrate that channel separately, but all channels that use that range are also automatically calibrated.

Calibrating Current

When calibrating the IOLAN Analog input for current, you will need a calibration meter that is better than .1% current precision. Each channel needs to be calibrated individually.

Calibrating Temperature Input

To calibrate an Analog (Temperature) input channel, read the section that applies to the type of input you are calibrating. Note that calibration will be done for the active channel configuration; for example, if Channel A1 is set to thermocouple, you cannot calibrate it for RTD. During the calibration process, you will be asked to apply the minimum and maximum range value to the channel in either mV or Ohms; for example, to calibrate for thermocouple J 0 to 760C, you will be prompted to first apply -80mV and then +80mV to the channel.

Also, you cannot actively calibrate disabled channels (although if you enable the channel and then set it for the type of thermocouple or RTD that has already been calibrated on another channel, it will also be calibrated).

Calibrating Thermocouple

When calibrating the IOLAN Analog input for thermocouple, you will need a calibration meter that is better than .15% accuracy. When you calibrate one channel, all thermocouple channels are automatically calibrated for that range; if another channel is set for a different range, you will need to calibrate that channel separately, but all channels that use that range are automatically calibrated.

176

IOLAN DS1/TS2 User’s Guide, Version 3.4

Page 176
Image 176
Perle Systems TS2, DS1 manual Calibrating I/O, Calibrating Analog Input, Calibrating Temperature Input

DS1, TS2 specifications

Perle Systems TS2 and DS1 are advanced serial-to-Ethernet devices designed to facilitate seamless integration of serial devices with modern IP networks. These devices serve as crucial tools for businesses looking to enhance their communication capabilities while leveraging existing infrastructure.

One of the standout features of the Perle TS2 and DS1 is their ability to support multiple serial protocols including RS232, RS422, and RS485. This versatile support allows businesses to connect various legacy devices to their networks, ensuring that critical equipment can still communicate effectively in an increasingly digital landscape.

The TS2 model is particularly noted for its dual serial ports, enabling simultaneous communication with multiple devices. This capability is invaluable for applications requiring real-time data transmission, such as remote monitoring and automated control systems. The DS1 model, on the other hand, is designed for single-port use, making it an ideal solution for smaller-scale operations or specific single-device connections.

Both the TS2 and DS1 incorporate advanced features such as configuration through a web interface, which simplifies setup and management. Users can easily access device settings and monitor performance metrics remotely, enhancing operational efficiency. These devices also support various network protocols such as TCP/IP, UDP, and ICMP, ensuring compatibility with a wide range of network architectures.

In terms of security, Perle Systems prioritize user data protection. The TS2 and DS1 offer features including SSL encryption and SSH protection, providing an added layer of security for sensitive information transmitted over the network. This is particularly important for industries where data integrity and security are paramount, such as healthcare and finance.

Additionally, the rugged design of both devices ensures reliable performance even in harsh environments. With extended temperature ratings and robust housing, the TS2 and DS1 can operate in diverse conditions without compromising functionality.

To summarize, the Perle Systems TS2 and DS1 provide a reliable and flexible solution for connecting legacy serial devices to modern networks. With their support for multiple serial protocols, web-based management, robust security features, and rugged design, these devices cater to a variety of industries looking to modernize their communication infrastructure while maintaining existing equipment. Whether for large-scale operations or smaller implementations, the TS2 and DS1 equip businesses with the tools needed for effective serial communication in an IP-driven world.