1. Prepare the UPS to connect the battery pack(s).2. Note the hotes used to attach the battery pack connector clamp.3. Insert the battery pack connector into the UPS.To install additional battery packs, repeat this procedure using the battery packconnectors on the battery packs.Note: Do not stack battery packs.
14. Specifications
MODEL SMK SMK SMK SMK SMK SMK
600A 800A 1000A 1250A 1500A 2000A
Capacity 600VA 800VA 1000VA 1250VA 1500VA 2000VA
Volta
g
e 100V, 110V, 120V, 220V, 230V, 240V, +/-25%,Sin
g
le
p
hase
INPUT
Fre
q
uenc
y
50 or 60Hz +/-5%
(
auto sensin
g)
Voltage
(on battery)
Pure sine wave output at nominal +/-5%
Frequency
(on battery)
50 or 60Hz +/-0.5%
OUTPUT
Voltage
Regulation
AVR
AVR automatically increase output voltage 15% above input
voltage if -9% to-25% of nominal. AVR decrease output voltage
15% below input voltage if+9% to +25% of nominal
S
p
ike Protection 320 Joules, 2ms
Unit Input Fuse for overload & short circuit protection
EMI/RFI filter 10dB at 0.15MHz
,
50dB at 30MHz
Overload
Protection
UPS automatic shutdown if overload exceeds 110% of nominal at
20 second and 125% at 2 seconds.
Transfer Time 2/4 milliseconds, including detection time
PROTECTION
AND
FILTERING
Short Circuit UPS output cut off immediately or input fuse protection
Type Hot swappable, Sealed, Maintenance-free lead acidBATTERY
Typical
Rechar
g
e Time
4 hours (to 90% of full capacity)
RED