WALL-MOUNTED BYPASS SWITCH INSTALLATION

12.Hardwire the UPS input terminations.

See Table 2 for specifications and Figure 22 for a detailed view of the UPS terminal block.

NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty.

NOTE The Powerware 9355 UPS is a single-feed UPS only.

Table 2. UPS Terminal Block Wiring

10 kVA

Wire

Input Circuit

L1, L2, L3, N

Ground

Tightening

Conduit Size2, 3

 

Input Voltage

Function

Breaker Size

Wire Size1

Wire Size1

Torque

(Number of Conduits)

 

208

Input

45A

6 AWG

10 AWG

120 lb in

1.00” conduit (1)

 

 

 

 

 

 

 

 

 

 

220

 

45A

8 AWG

10 AWG

(13.5 Nm)

 

 

 

 

 

 

 

 

 

 

 

208

Output

 

8 AWG

10 AWG

120 lb in

1.00” conduit (1)

 

 

 

 

 

 

 

 

 

 

220

 

 

8 AWG

10 AWG

(13.5 Nm)

 

 

 

 

 

 

 

 

 

 

 

15 kVA

Wire

Input Circuit

L1, L2, L3, N

Ground

Tightening

Conduit Size2, 3

 

Input Voltage

Function

Breaker Size

Wire Size1

Wire Size1

Torque

(Number of Conduits)

 

208

Input

60A

4 AWG

10 AWG

120 lb in

1.25” conduit (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220

 

60A

4 AWG

10 AWG

(13.5 Nm)

1.25” conduit (1)

 

 

 

 

 

 

 

 

208

Output

 

6 AWG

10 AWG

120 lb in

1.00” conduit (1)

 

 

 

 

 

 

 

 

 

 

220

 

 

6 AWG

10 AWG

(13.5 Nm)

 

 

 

 

 

 

 

 

 

 

 

 

1Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.

2 Per NEC article 300-20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the phase conductors.

3 Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.