12.Hardwire the UPS input terminations.
See Table 2 for specifications and Figure 22 for a detailed view of the UPS terminal block.
NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty.
NOTE The Powerware 9355 UPS is a
10 kVA | Wire | Input Circuit | L1, L2, L3, N | Ground | Tightening | Conduit Size2, 3 |
|
Input Voltage | Function | Breaker Size | Wire Size1 | Wire Size1 | Torque | (Number of Conduits) |
|
208 | Input | 45A | 6 AWG | 10 AWG | 120 lb in | 1.00” conduit (1) | |
|
|
|
|
| |||
|
|
|
|
| |||
220 |
| 45A | 8 AWG | 10 AWG | (13.5 Nm) | ||
|
|
| |||||
|
|
|
|
|
|
|
|
208 | Output |
| 8 AWG | 10 AWG | 120 lb in | 1.00” conduit (1) | |
|
|
|
|
| |||
|
|
|
|
| |||
220 |
|
| 8 AWG | 10 AWG | (13.5 Nm) | ||
|
|
|
| ||||
|
|
|
|
|
|
| |
15 kVA | Wire | Input Circuit | L1, L2, L3, N | Ground | Tightening | Conduit Size2, 3 |
|
Input Voltage | Function | Breaker Size | Wire Size1 | Wire Size1 | Torque | (Number of Conduits) |
|
208 | Input | 60A | 4 AWG | 10 AWG | 120 lb in | 1.25” conduit (1) | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
220 |
| 60A | 4 AWG | 10 AWG | (13.5 Nm) | 1.25” conduit (1) | |
|
|
|
|
|
|
|
|
208 | Output |
| 6 AWG | 10 AWG | 120 lb in | 1.00” conduit (1) | |
|
|
|
|
| |||
|
|
|
|
| |||
220 |
|
| 6 AWG | 10 AWG | (13.5 Nm) | ||
|
|
|
| ||||
|
|
|
|
|
|
|
|
1Use only
2 Per NEC article
3 Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW,
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com | 33 |