OPERATION

User Settings

The following table displays the options that can be changed by the user.

NOTE Changes to the output voltage or frequency options should be made before turning on the UPS; otherwise, the changes do not take effect.

Table 8. User Settings

Description

 

Available SettingsDefault Setting

 

 

 

 

 

Set Date and Time

Set Month

01/01/2003

 

 

 

Date: mm/dd/yyyy

 

 

 

Time: 24:00

00:00

 

 

 

 

Display Contrast

Adjust contrast with up/down arrow

Moderate

 

 

buttons

 

 

 

 

 

Change Language

Select Language:

English

 

 

<English> or <Spanish>

 

 

 

 

 

Set Nominal Input Voltage

Output:

120V/208V

 

 

[120V/208V] [127V/220V]

 

 

 

 

 

 

Relay Config

 

Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or

Alarm 1: empty

 

 

[X-Slot 2-1/2/3/4]

X-Slots (1 or 2)

 

 

Setup: [Battery Low] [On Battery] [On

#1: UPS ok

 

 

Bypass] [UPS ok] [custom] [empty]

#2: On Bypass

 

 

 

#3: Summary Alarm

 

 

 

#4: On Battery

 

 

 

 

Signal Inputs

 

[empty] [Logic]

Empty

 

 

(see “Programmable Signal Inputs”

 

 

 

 

on page 62)

 

 

 

 

 

 

Serial Port Config

Port: [X-Slot-1] [X-Slot-2/Serv]

19200

 

 

 

Speed: [19200] [9600] [2400] [1200]

 

 

 

 

 

 

Start Screen

 

Eaton Powerware logo

Eaton Powerware logo

 

 

Mimic Screen

 

 

 

 

 

User Password

Enabled/Disabled

Disabled

 

 

If Enabled is selected, the password is

 

 

 

 

USER.

 

 

 

 

 

Audible Alarms

Normal Sound/Disabled

Normal Sound

 

 

 

Battery Charging

ABM cycling/constant

ABM cycling

 

 

68

EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com