Installation
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max).
With the exception of the
Before maintenance or repair, all connections must be removed. Before maintenance, repair, or shipment, the unit must be completely switched off and unplugged or disconnected.
C A U T I O N
Important Notice The UPS ground (earth) conductor carries leakage current from the loads in addition to any leakage current generated by the UPS. This UPS generates no more than 0.5 mA of current (120V Model), or 1 mA of current (230V Model).
To limit the total leakage current to 3.5 mA, the load leakage must be limited to 3 mA on the 120V Model and 2.5 mA on the 230V Model.
If you do not know the load leakage current, replace the UPS power cord
(230V Model only) with a power cord that uses a locking plug with a minimum rating of 10A (such as IEC 309).
If you do not have a matching receptacle, consult an electrician to install the proper receptacle.
The
Quick Startup
The Powerware 3110 provides protection against many power problems, including power outages. It also provides spike suppression and line noise filtering to protect your equipment.
1.On 230V Models, plug the UPS power cord into the input connector on the UPS side panel.
2.Plug the equipment to be protected into the UPS output receptacles.
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
2 | Powerware® 3110 User's Guide 05147486 B (English) Uncontrolled Copy |