OPERATION
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
www.powerware.com
53
Table 4. Output Settings
Function Factory Setting Options Comments
Output Voltage EU Models: 230V
U Models: 208V
200V / 208V / 220V /
240V / 250V
Freq Converter Disable Enable
Output Frequency EU Models: 50 Hz
U Models: 60 Hz
60 Hz User selectable under
frequency−converter mode
Eco Mode Disable Enable See page 50
Slew Rate 1 Hz / sec 0.5 Hz / sec
Bypass Transfer
If bypass Ac nok?
Yes No Transfer to bypass if utility power is
out of tolerance
Interrupt Time 10 ms 20 ms, ...... , 200 ms Break time calibration during load
transfer on utility power out of
tolerance
Overload Prealarm 105% 40%, 50%, 70% Alarm if threshold is overrun
Table 5. ON/OFF Settings
Function Factory Setting Options Comments
Cold Start Disable Enable Start on battery
Forced Reboot Enable Enables automatic restart of the
system even if utility power is
restored before the end of the
shutdown sequence
Auto Restart Enable Disable UPS restarts automatically when
utility power is restored
Energy Saving Disable Enable Automatic shutdown on battery if
output load level <10%
Sleep Mode Enable Disable
Remote Command Enable Disable Enables consideration of shutdown or
restart orders from software to be
authorized