SPECIFICATIONS
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
www.powerware.com
66
Table 12. Power Connections
Model Input Connection Output Receptacles
U Models 10 ft, L6−30P power cord (4) NEMA L6−30R
EU Models Hardwired Hardwired with
(8) 10A, IEC 320−C13; (2) 16A, IEC 320−C19
Table 13. Environmental and Safety
U Models EU Models
Operating Temperature 0°C to 40°C (32°F to 104°F)
Storage Temperature −25°C to 40°C (−13°F to 104°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 1,000 meters above sea level
Audible Noise Less than 46 dBA Normal mode, typical load and Battery mode
Surge Suppression ANSI C62.41 Category B, IEC 61000−4−5
Safety Conformance UL 1778;
CSA C22.2, No. 107.1;
NOM−019−SCFI
UL 1778;
CSA C22.2, No. 107.1;
EN 62040−1−1, IEC 60950−1, IEC 50091−1−1
Agency Markings cUL, NOM TUV(GS), CE, cUL, C−tick
EMC (Class A) FCC Part 15 EN 62040−2 C1, AS 62040−2 C1, FCC Part 15
Table 14. Battery
UPS Configuration (15) 12V, 5.5 Ah internal batteries
EBM Configuration (2 strings of 15) 12V, 5.5 Ah internal batteries
Type Sealed, maintenance-free, lead-acid
Table 15. Battery Runtimes
UPS UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
5000 VA 5 min 22 min 41 min 1 hr 2 min 1 hr 23 min
6000 VA 4 min 17 min 33 min 50 min 1 hr 7 min
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.