Powerware 8 - 10 kVA, 8 - 15 kVA Maintenance, Regular service/intervals, Scrapping, Batteries

Models: 8 - 15 kVA 8 - 10 kVA

1 46
Download 46 pages 28.02 Kb
Page 36
Image 36

8. Maintenance

All operations inside the unit must be performed only by a service engineer from the manufacturer or from an agent, authorised by the manufacturer.

The troubleshooting procedure gives simple remedial if a malfunction occurs in the UPS. The operator should start the trouble shooting if there is an active alarm indicated on the LCD screen. Service should be contacted if the active alarm is abnormal and displayed as a service code.

Call service if you are not able to solve the problem.

LCD display

Description

Action

 

 

 

 

The connected load needs more

Shut down the least important load

 

that is connected to the UPS. The UPS

 

power than the UPS is rated to

Overload

should switch back to normal

provide. The inverter or static bypass

 

operation once the load level is

 

is supplying the excessive load level.

 

acceptable.

 

 

 

Your batteries are detected to be

Batteries should be replaced and you

Battery test failed

need to contact the local office or

faulty.

 

representative of the UPS manufacturer.

 

 

 

The UPS is operating in stored energy

Make controlled shutdown of the

Battery low

mode. It will shut down soon due to

protected load immediately to prevent

 

low battery voltage.

loss of data.

 

The UPS is operating in stored energy

Save your data and perform a

On battery

controlled shutdown of your server

mode.

 

load.

 

 

 

 

Check that fans are operational and

Overtemperature

High UPS temperature is detected.

ventilation holes are not blocked. Make

sure the ambient temperature is not

 

 

 

 

excessive

Table 41. Typical alarms displayed in the LCD screen of the UPS unit.

Scrapping

Before scrapping UPS or its battery cabinet, the battery bank must be removed. Local requirements must be followed in battery recycling or discard. The removal of batteries is allowed only by authorised service personnel due to high energy and voltage.

Regular service/intervals

The UPS requires very little maintenance if installed in an appropriate environment.

Maintentenance

Interval

Batteries change

~ 3-5 years / service

 

 

Batteries test

~ 18 months / service

 

 

Cooling fan change

~ 5 years / service

Table 42. Routine maintenance intervals recommended by the manufacturer.

Batteries

The condition of the batteries is crucial for operation. The UPS will indicate by audible and visual alarms if the capacity of the battery bank has decreased. The UPS units are provided with the automatic battery test and ABM management function to continuously monitor the condition of the battery bank.

36

UPS 8 – 15 kVA, 230V 50/60 Hz output

1022403

 

User’s Guide

Revision B1

Page 36
Image 36
Powerware 8 - 10 kVA, 8 - 15 kVA manual Maintenance, Regular service/intervals, Scrapping, Batteries