10. Technical data
Standards
UPS | 8 kVA |
| 10 kVA |
| 12 kVA |
| 15 kVA |
Safety |
| IEC |
| ||||
|
|
|
|
|
|
|
|
EMC |
|
|
| EN |
| ||
|
|
|
|
|
|
| |
Product |
|
| IEC |
| |||
|
|
|
|
|
|
|
|
Environment
UPS | 8 kVA |
| 10 kVA | 12 kVA |
| 15 kVA |
Amb. temperature |
| 0 to +40°C (electronics), 15 to +25°C (batteries) |
| |||
|
|
|
|
|
|
|
Relative humidity |
|
| 0 to 95%, no condensation allowed |
| ||
|
|
|
|
|
|
|
Altitude |
|
| <1000 m above sea level at +40°C |
| ||
|
|
|
|
| ||
Vibration | IEC | |||||
|
|
|
|
|
|
|
Mechanical configuration
UPS |
| 8 kVA |
| 10 kVA |
| 12 kVA |
| 15 kVA | ||
Dimensions |
|
|
|
|
|
|
|
|
| |
- Width |
|
|
|
|
| 305 mm |
|
| ||
- Depth |
|
|
|
|
| 702 mm |
|
| ||
- Height |
|
|
| 817 mm (32 bat) or 1214 mm (2x32 bat) | ||||||
Weight |
|
|
|
|
|
|
|
|
| |
- no battery |
|
|
| 65 kg |
|
| 70 kg | |||
- 32 battery |
|
|
| 155 kg |
|
| 160 kg | |||
- 64 battery |
|
|
| 265 kg |
|
| 270 kg | |||
- 32 battery and transformer |
|
| 270 kg |
|
| 275 kg | ||||
- MBS |
|
|
|
|
| +15 kg |
|
| ||
Colour |
|
|
|
| RAL 9005 black |
|
| |||
Characteristics |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||
UPS | 8 kVA |
| 10 kVA |
| 12 kVA |
| 15 kVA | |||
Efficiency | Up to 92% |
| Up to 93% |
| Up to 92% |
| Up to 93% | |||
- nominal load |
|
|
| |||||||
|
|
|
|
|
|
|
|
| ||
Heat losses | <580 W |
| <720 W |
| <870 W |
| <1050 W | |||
|
|
|
|
|
|
| ||||
Backup time | 10 min (32 bat 7 Ah) | 6 min (32 bat 7 Ah) |
|
|
|
| ||||
15 min (32 bat 9 Ah) | 10 min (32 bat 9 Ah) | 8 min (32 bat 9 Ah) | 5 min (32 bat 9 Ah) | |||||||
- load pf 0.7 | ||||||||||
28 min (64 bat 7 Ah) | 20 min (64 bat 7 Ah) | 15 min (64 bat 7 Ah) | 10 min (64 bat 7 Ah) | |||||||
(+25°C amb.) | ||||||||||
33 min (64 bat 9 Ah) | 25 min (64 bat 9 Ah) | 20 min (64 bat 9 Ah) | 15 min (64 bat 9 Ah) | |||||||
| ||||||||||
Noise (ISO 7779) |
|
|
| 50 - 53 dB(A) depending on the load |
|
|
1022403 | UPS 8 – 15 kVA, 230V 50/60 Hz output | 43 |
Revision B1 | User’s Guide |
|