AC input
UPS | 8 kVA |
| 10 kVA |
| 12 kVA | 15 kVA |
Rectifier input |
|
|
|
|
|
|
- S/SC model |
|
| - | - | ||
- N/NC model |
|
| ||||
Bypass input |
|
|
| 1 phase |
| |
|
|
|
|
| ||
Voltage |
| 192 to 253 Volts without using battery |
| |||
Frequency |
|
|
| 45 to 65 Hz |
| |
|
|
|
|
|
|
|
Power factor |
|
|
| 0.99 |
| |
|
|
|
|
|
| |
Input distortion |
|
| < 5% THD(I) |
| ||
Rated input current |
|
|
|
|
|
|
- | 11,6 A |
| 14,5 A |
| 17,4 A | 21,8 A |
- | 34,8 A |
| 43,5 A |
| - | - |
DC circuit
UPS | 8 kVA | 10 kVA |
| 12 kVA | 15 kVA |
Management |
| Advanced Battery Management |
| ||
|
|
|
|
|
|
Nominal voltage |
|
| 384 Volts |
| |
|
|
|
|
|
|
Battery qty |
|
| 32 pcs. |
| |
|
|
|
|
|
|
Float voltage |
|
| 2.30 VPC |
| |
Battery type |
| VRLA 12 Volts |
| ||
Cut off voltage |
|
| 1.75 VPC |
| |
|
|
|
|
| |
Battery charging |
| 3 amps, user selectable |
|
AC output
UPS | 8 kVA | 10 kVA |
| 12 kVA | 15 kVA |
Active power | 7,2 kW | 9 kW |
| 10,8 kW | 13.5 kW |
Nro. of phases |
|
|
| ||
Frequency |
| 50 Hz or 60 Hz, user selectable |
| ||
Voltage |
| 220, 230 or 240 Volts, user selectable |
| ||
|
|
|
|
|
|
Short circuit | 100 A, < 300 ms |
| 144 A, < 300 ms | ||
capability |
| ||||
|
|
|
|
| |
|
| 10 min |
| ||
Overload capability |
| 1 min > |
| ||
| 5 sec |
| |||
|
|
| |||
|
| 300 ms >150% load |
|
44 | UPS 8 – 15 kVA, 230V 50/60 Hz output | 1022403 |
| User’s Guide | Revision B1 |