Powerware 8 - 15 kVA, 8 - 10 kVA manual Wiring procedure, Installation procedure

Models: 8 - 15 kVA 8 - 10 kVA

1 46
Download 46 pages 28.02 Kb
Page 15
Image 15

Contact the manufacturer’s authorised agent or the local office for assistance at fuse and cable sizing. Refer to the recommended cable and fuse ratings in the below table.

UPS rating

 

Input

 

 

Bypass

 

Load

 

PE

Battery

 

Fusing

Cable

Fusing

Cable

Cable

I nom

Cable

Cable

 

 

8 kVA

3-phase

3x16

A

3x2.5 mm²

50 A

10 mm²

10 mm²

34.8 A

10 mm²

10 mm²

 

1-phase

50 A

 

10 mm²

50 A

10 mm²

10 mm²

34.8 A

10 mm²

10 mm²

10 kVA

3-phase

3x16

A*

3x2.5 mm²

50 A

10 mm²

10 mm²

43.5 A

10 mm²

10 mm²

 

3-phase

3x20

A

3x4 mm²

50 A

10 mm²

10 mm²

43.5 A

10 mm²

10 mm²

 

1-phase

63 A

 

16 mm²

50 A

10 mm²

10 mm²

43.5 A

10 mm²

10 mm²

12 kVA

3-phase

3x25

A

3x6 mm²

63 A

16 mm²

16 mm²

52.2 A

16 mm²

10 mm²

15 kVA

3-phase

3x25

A*

3x6 mm²

80 A

25 mm²

25 mm²

65.2 A

16 mm²

10 mm²

 

3-phase

3x32

A

3x10 mm²

80 A

25 mm²

25 mm²

65.2 A

16 mm²

10 mm²

Maximum

3-phase

3x63

A

3x16 mm²

80 A

35 mm²

35 mm²

 

35 mm²

16 mm²

Table 14. Cable and fuse ratings for the different UPS ratings

(*With optional limited charging feature at low input and high kW load, see User Settings)

Wiring procedure

The power cable terminals are located in the back of the UPS unit. The service personnel is responsible for the correct electrical installation. They must be authorised by the manufacturer.

The installation procedure:

1.Remove the cover(s) of the terminal box of the power cables with a screwdriver. Refer to the dimensional drawing for the correct location at the back of the unit.

2.Slide the cables through the grommets of the connection box.

3.Connect the conductors of the rectifier and bypass input cables to the proper terminals. With single phase unit it is recommended to use the same phases for rectifier and bypass inputs.

4.Connect the conductors of the load cable to the proper terminals.

5.Connect the conductors of an external battery cabinet cable to the external battery +, - and PE terminals. Check for the correct polarity.

See External Battery Cabinet (EBC) installation procedure.

Warning!

If available, the internal battery has to be disconnected first because the external battery terminals are hazardous due to the parallel battery string.

6.Secure the cables with the grommets in the connection box.

7.Fasten the cover of the terminal box with a screwdriver.

The IEC/EN 62040-1 safety instructions require the fitting by the user of a warning label on all primary power isolators installed remote from the UPS area. The warning label for electrical maintenance personnel shall carry the following wording or equivalent:

“ISOLATE UNINTERRUBTIBLE POWER SUPPLY (UPS) BEFORE WORKING ON THIS CIRCUIT.”

A readily accessible disconnect device shall be incorporated in the building installation wiring as shown in diagrams.

1022403

UPS 8 – 15 kVA, 230V 50/60 Hz output

15

Revision B1

User’s Guide

 

Page 15
Image 15
Powerware 8 - 15 kVA, 8 - 10 kVA manual Wiring procedure, Installation procedure

8 - 15 kVA, 8 - 10 kVA specifications

Powerware 8 - 10 kVA and 8 - 15 kVA are robust uninterruptible power supply (UPS) systems designed to provide reliable power protection and enhanced performance for critical applications. These UPS systems are ideal for various business environments, including data centers, server rooms, and industrial settings.

A primary feature of the Powerware series is its modular design, which allows for easy scalability and adaptability to meet the growing power requirements of modern IT infrastructure. The systems can be configured to provide redundancy, ensuring increased reliability and uptime while delivering high-efficiency performance.

One of the standout characteristics of the Powerware 8 - 10 kVA and 8 - 15 kVA models is their advanced double-conversion technology, which offers consistent power conditioning and isolation from utility issues like voltage surges, frequency variations, and power outages. This technology ensures that connected devices receive clean, stable power, minimizing the risk of downtime caused by electrical disturbances.

Another key feature is the availability of an intuitive LCD display that provides users with real-time information about the UPS status, critical alarms, and event logs, enabling proactive management of power demands and potential issues. The systems also support remote monitoring and management through advanced communication options, allowing IT administrators to maintain oversight of the power environment from any location.

The Powerware series incorporates high-efficiency designs that help reduce energy consumption, ultimately lowering operational costs. With an input power factor of up to 0.99 and a typical efficiency exceeding 94%, these UPS units not only contribute to environmental sustainability but also enhance the overall performance of the power infrastructure.

In addition to these practical features, the Powerware 8 - 10 kVA and 8 - 15 kVA models are equipped with multiple output options, including configurable outlets and hardwire connections, offering flexibility in deployment. They also come with advanced battery management systems, which optimize battery performance, extending their lifespan and reducing maintenance efforts.

Overall, Powerware 8 - 10 kVA and 8 - 15 kVA systems are reliable choices for businesses seeking efficient and adaptable power protection solutions to support their critical operations. Their innovative technologies and comprehensive features ensure that companies can maintain productivity while safeguarding their valuable equipment and data against power disruptions.