Premier Fire Alarm Control Panel Installation & Commissioning Recommendations, Soak Test

Models: Fire Alarm Control Panel

1 22
Download 22 pages 59.32 Kb
Page 19
Image 19
INSTALLATION & COMMISSIONING RECOMMENDATIONS

PREMIER SX USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Measures incorporated to limit false alarms. Account has to be taken of the guidance contained in section 3 of BS 5839-1: 2002 and, more specifically (tick as appropriate):

SOAK TESTVERIFICATION The System is manual. Type & siting of manual call points takes account of the guidelines contained in section 3 of BS 5839-1

MAINTENANCEUSER RESPONSIBILITIES The system incorporates automatic fire detectors, and account has been taken of reasonably foreseeable causes of unwanted alarms, particularly in the selection and siting of detectors

Manual backgroundManual background An appropriate analogue system has been specified

Manual backgroundManual backgroundManual background An appropriate multi-sensor system has been specified

Manual backgroundManual backgroundManual background A time-related system has been specified. Details:

Manual backgroundManual background Fire signals from automatic fire detectors result initially in a staff alarm, which delays a general alarm / transmission of signals to an alarm receiving centre (delete as applicable)

for min.

Manual backgroundManual backgroundManual background Appropriate guidance has been provided to the user to enable limitation of false alarms.

Manual backgroundManual background Other measures as follows:

INSTALLATION & COMMISSIONING RECOMMENDATIONS

It is strongly recommended that installation and commissioning be undertaken in accordance with the recommendations of section 4 and section 5 of BS 5839-1: 2002 respectively.

SOAK TEST

Manual backgroundManual backgroundManual background In accordance with the recommendations of clause 35.2.6 of BS 5839-1:2002, it is recommended

that following commissioning a soak period ofshould follow (enter a period of at least 1 week)

Manual backgroundManual background As the system incorporates no more than 50 automatic fire detectors, no soak test is necessary to satisfy the recommendations of BS 5839-1:2002

VERIFICATION

Verification that the system complies with BS 5839-1:2002 should be carried out, on completion, in accordance with BS 5839-1:2002 Clause 43

Yes

 

No

 

To be decided by the purchaser or user

 

 

 

 

MAINTENANCE

It is strongly recommended that, after completion, the system is maintained in accordance with section 6 of BS 5839-1:2002

USER RESPONSIBILITIES

The user should appoint a responsible person to supervise all matters pertaining to the fire alarm system in accordance with the recommendations of section 7 of BS 5839-1:2002

Approved Document No: GLT.MAN-102

PAGE 19

Issue: 1.3 Authorised: GH

Date: 9/6/2004

 

Page 19
Image 19
Premier Fire Alarm Control Panel Installation & Commissioning Recommendations, Soak Test, Verification, Maintenance