7. DISABLEMENTS

7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM.

Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is possible for the user to disable that zone during the risk period and then enable it again afterwards. During a disablement of a zone(s), no fire or fault signal will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled, that is zones already in fire cannot be disabled.

External sounders can also be disabled as could be required in certain conditions.

7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS.

1.Turn control key to “Controls Enable” position;

2.Press “Engineer” switch momentarily, this will cause General Disablement LED to flash (fast). This means the panel is in disable/enable mode;

3.Press scroll (No. 4) switch once and this will cause the General Disablement LED to flash (slow);

4.Press scroll (No. 4) switch once again and this will cause Zone 1 Disablement LED to light steady;

5.Pressing scroll (No. 4) switch will cause the zone disablement LED to toggle to zone 2 and so on;

 

 

 

FIRE / ZONES

 

 

 

 

 

 

 

 

 

 

2

3

4

5

6

7

8

POWER

SUPPLY

FLT

 

 

 

 

 

 

 

 

GEN-FIRE

 

DEL

ZONAL

/ DISABLEMENT / TEST

 

 

 

 

 

 

1

2

3

4

5

6

7

8

GEN-FAULT

SYSTEM FLT

GEN-S/C

 

 

 

 

 

 

 

 

STOP-START

SILENCE

RESET

SCROLL /

 

 

 

 

 

 

1

2

3

4

ENGINEER

 

GEN-ZONE TEST

 

 

 

 

 

 

 

 

 

FLT TONE

 

 

/ LED TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

GEN-DISABLEMENT DELAY

 

 

 

 

 

 

 

 

 

 

OVERRIDE

 

6.Select zone to be disabled. For example, if Zone 3 is selected and with Zone 3 disablement LED lit (steady) and General Disablement LED flashing slow, pressing “Engineer” will cause General Disablement LED light to change to steady. This means that zone 3 is now disabled;

7.Switch controls key to off position, then both the disabled Zone Disablement LED and the General Disablement LED will remain lit (steady.

7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS.

1.Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED with stay lit (steady);

2.Press “Engineer” switch once and this will cause the General Disablement LED to flash (fast);

3.Press scroll (No. 4) switch until the light is steady at the disabled zone;

4.Press “Engineer” and this will cause the General Disablement LED to flash (slow);

5.Turn control Key to “Off” position and this will turn off the General Disablement and Zone Disablement LEDs.

NOTES:

The option of disabling or enabling zones 2, 3, 4, 5, 6, 7 and 8 is only available if these zones are present on the panel

Approved Document No: GLT.MAN-102