4.3SUMMARY OF LED COMBINATIONS AND THEIR MEANING Use the table below to determine the condition of the panel.

LEDs LIT

LED CONDITION

PANEL STATUS

POWER

CONSTANTGREEN

The panel is supplied with power, and has no faults / fires (System Normal)

 

 

 

GEN FLT

CONSTANTYELLOW

Problem with keyswitch connections

ONLY

 

 

 

 

 

GEN FLT &

CONSTANTYELLOW

There is a problem with either the mains supply or the battery backup

SUPPLY FLT

FLASHINGYELLOW

 

 

 

 

GEN FLT &

CONSTANTYELLOW

There is a wiring problem. One of the cables is touching the earth screen.

EARTH FLT

FLASHINGYELLOW

 

 

 

 

GEN FLT &

CONSTANTYELLOW

There is an open circuit fault in the wiring of the zone indicated.

ZONAL FLT

FLASHINGYELLOW

 

 

 

 

GEN FLT &

CONSTANTYELLOW

There is a short circuit fault in the wiring of the zone indicated.

ZONAL FLT

FLASHINGYELLOW

 

GEN S/C

FLASHINGYELLOW

 

 

 

 

GEN FLT &

CONSTANTYELLOW

There is an open circuit fault in the wiring of one or both of the sounder

SND FLT

FLASHINGYELLOW

circuits

 

 

 

GEN FLT &

CONSTANTYELLOW

There is a short circuit fault in the wiring of one or both of the sounder

SND FLT

FLASHINGYELLOW

circuits

GEN S/C

FLASHINGYELLOW

 

 

 

 

GEN FLT &

CONSTANTYELLOW

A processor fault has occurred. To reset, turn keyswitch on then back off. If

SYSTEM FLT

CONSTANTYELLOW

problem persists, consult your dealer.

 

 

 

GEN FIRE

CONSTANTRED

A manual evacuation has occurred.

ONLY

 

The sounders will be active.

 

 

 

GEN FIRE &

CONSTANTRED

A fire has occurred in the zone indicated.

ZONE FIRE

CONSTANTRED

The sounders will be active.

 

 

 

GEN FIRE &

CONSTANTRED

A fire has occurred in the zone indicated.

ZONE FIRE &

CONSTANTRED

The sounders have a delay set, and will become active after the

GEN DISABLE

CONSTANTYELLOW

programmed delay. To override the display, press delay override.

& DEL

CONSTANTYELLOW

 

 

 

 

GEN DISABLE

FLASHINGYELLOW

The panel is ready for selecting disable or test mode

 

(FAST–4HZ)

 

 

 

 

GEN DISABLE

FLASHINGYELLOW

The panel is in SELECT DISABLEMENT MODE

 

(SLOW–0.5HZ)

 

 

 

 

GEN DISABLE

FLASHINGYELLOW

The user is scrolling through zones to select which one to disable/or user

ZONEDISABLE

(SLOW–0.5HZ)

has just enabled the zone.

 

 

 

GEN DISABLE

CONSTANTYELLOW

The indicated zone is disabled.

ZONEDISABLE

CONSTANTYELLOW

 

 

 

 

GEN DISABLE

CONSTANTYELLOW

The Sounders are delayed by the amount set on the rotary switch.

DEL

CONSTANTYELLOW

 

 

 

 

GEN TEST

FLASHINGYELLOW

The indicated zone is in Test Mode.

ZONEDISABLE

FLASHINGYELLOW

 

 

(VERYSLOW–0.25HZ)

 

 

 

 

4.4 CHECKING THE PANELS INDICATION LEDS

Turn the key switch to “Controls Enabled” position then press the LED test button (Button 4). All the LEDs on the front panel will light, and the panel’s internal buzzer will also sound.

Approved Document No: GLT.MAN-102

PAGE 6

Issue: 1.3 Authorised: GH

Date: 9/6/2004

 

Page 6
Image 6
Premier Fire Alarm Control Panel user manual LED Condition Panel Status, Checking the Panels Indication Leds