6.0 CONTROL PANEL OPERATION

PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501

G5C Dryers

Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com psb@genair.net

 

6.0 CONTROL PANEL OPERATION

These dryers are equipped with an electronic controller. Please note that the SET POINT & other control parameters have been optimized and factory set. Altough the set point value can be displayed, the ability to alter these factory settings via the digital interface on the front panel has been removed to eliminate the possiblity of unit damage caused by improper settings. A description of the operation of the digital interface is provided below however, to facilitate factory-authorized adjustments.

6.1 Status LEDs

DP1

On

DX solenoid energized

 

 

 

DP2

On

Condensate drain valve energized

 

 

 

DP3

On

Compressor energized

 

 

 

6.2 Button Functions

 

TEST

 

Performs a test of the condensate discharge valve when pressed for more than 3 seconds during the normal

 

 

operation.

 

 

 

 

 

 

 

 

SET

 

Displays the set point value when pressed during normal operation.

 

 

Stores all changes when pressed after changing set point.

 

 

 

 

 

 

 

 

DOWN

 

Decreases the displayed value when pressed during set point programming (see factory).

 

 

 

 

 

UP

 

Increases the displayed value when pressed during set point programming (see factory).

 

 

 

 

 

ON/OFF

 

Activates or deactivates unit operation when pressed for 3 seconds. When deactivated, the OFF message

 

 

is displayed.

 

 

 

 

 

 

 

6.3 Set Point Modification

Press the SET button (the current set point value is displayed).

Modify (see factory) the displayed set point value by using the UP or DOWN button (if modification is not performed in 15 seconds the controller automatically returns to the normal operating display indicating the DEW POINT value).

Confirm the new set value by pushing the SET button within 10 seconds of the modification, the flashing of the set point value confirms acceptance of the new data. If the modified data is not confirmed within 10 seconds, the new data will not be stored and the controller will revert to the previous set point.

Please note that changes to the set point WILL adversely effect dryer operation and therefore should only be done by authorized technical service personnel.