7.0 TROUBLESHOOTING

PSB INDUSTRIES INC. General Air Division 1202 West 12th Street, Erie, PA. 16501

G5C Dryers

Phone : 814-45—3651 Fax : 814-454-3492 www.PSBINDUSTRIES.com psb@genair.net

 

 

6.4

Digital Display

 

 

 

 

 

 

 

 

 

 

 

Message (NOT flashing)

Description

 

 

 

 

Numeric Value

Dewpoint Temperature

 

 

 

 

“ICE”

Energy Saving Standby Mode

 

 

6.5

Error Codes

 

 

 

The controller recognizes specific types of operational errors. When an error occurs the display shows a flashing alarm message alternating with the current dewpoint value, as described below:

Message (flashing)

Cause

HtA

High Dewpoint Temperature

PF1

Temperature Sensor failure

All the alarms except for PF1 are automatically reset when the cause is removed. PF1 must be cleared by switching the unit off and then re-started. PF1 has a priority over all the other displayed messages.

7.0 TROUBLESHOOTING

SYMPTOM

Temperature shown in display is higher than preset value

Excessive air pressure drop across dryer

Water present in air downstream of dryer

POSSIBLE ORIGIN

SOLUTION

High compressed air inlet temperature

Reduce air temperature to within design limits

High compressed air flow

Reduce air flow to within design limits

High ambient air temperature

Increase ventilation rate of installation area

Fouled refrigerant condenser

Clean condenser

Low refrigerant charge

Locate & repair leak & re-charge

Faulty refrigerant compressor

Repair or replace

Faulty refrigerant solenoid valve

Repair or replace

Faulty fan thermostat

Repair or replace

Faulty control relay

Repair or replace

Refrigerant high pressure switch open

Eliminate cause & reset switch

Inlet/outlet piping reversed

Connect properly

Thermostat sensor out of well

Re-install

Faulty thermostat

Repair or replace

Ambient temperature below freezing

Install dryer in heated space

Obstruction in air circuit

Locate & remove blockage

Air by-pass valve open

Close valve

Condensate drain strainer fouled

Clean strainer

Faulty condensate drain

Repair or replace

High dew point temperature

See Symptom #1 above