Gas Pressure Specifications
Type of | Inches WC | Regulator | |
|
| ||
Gas | Min. | Max.* | Setting |
|
| ||
|
|
|
|
Natural | 4.5 | 10.5 | 3.5 |
|
|
|
|
Propane | 12.0 | 13.0 | 11.0 |
|
|
|
|
*Do not exceed maximum inlet gas pressure. The minimum value shown is for input adjustment.
Table G: Gas Pressure Specifications
Gas Pressure Regulator
The gas valve is provided with pressure taps to meas- ure gas pressure upstream of the gas valve and downstream which is the same as the manifold pres- sure.
Water Connections & System Piping
The pipe size and fittings between the heater and the tank should be at least 1" for model 0090, and
If this water heater is installed in a closed water supply system, such as one having a
Fig. 7: Heater with Storage Tank
12