Models | X |
|
|
7.0″ | |
|
|
13.20″ | |
|
|
LEFT SIDE
Fig. 3: Component Locations — Hi Delta
NOTE: If a “DIP” switch is provided on the control
PCB, verify that the switch settings are correct: 1 = OFF, 2 = ON, 3 = OFF.
OPERATION
Verify the following upon a CALL FOR HEAT signal from the heater:
1.CALL FOR HEAT LED on PCB illuminates GREEN.
2.START UP MODE LED on PCB illuminates YEL- LOW. Before 7 minutes it should go out if boiler inlet temperature is approaching the set point tem- perature.
CALL FOR HEAT
START UP MODE
INLET TEMP ERROR
SENSOR OUT OF RANGE
Connecting Power to the Controller
Supply power from the 120 VAC power input from the heater to the controller power inputs Terminal Block (TB1). This is accomplished by connecting wiring from the control box to the heater TB1 board 120 VAC power input connections. Refer to wiring diagrams.
Set
Point
Pot
Fig. 5: Control PCB
3.The “ACTUATOR” should be in the fully open posi- tion or move to the fully open position if not already
there. (Actuator at the fully CCW position)
4.Before 7 minutes time has elapsed if the control is operating properly the “START UP MODE” LED
should go out. The inlet water temperature should be stable at a temperature between 105° F and 120° F (Normally set to 110° F) cooresponding to the Set Point Pot setting on the PCB. The actuator should have stopped moving.
Reset Switch
Fig. 4: Location of TB1 in Control Box
5