3)Pilot Outage.

1) Too low or too high gas

1)

Adjust inlet gas pressure as

 

(Standing pilot models)

 

pressures.

 

shown on rating plate.

 

 

2)

Restricted pilot.

2)

Clean pilot orifice.

 

 

3)

Weak thermocouple.

3)

Replace thermocouple.

 

 

 

 

 

4)Yellow lazy flame.

1) Too low gas pressure.

1) Adjust manifold pressure as

 

 

 

 

 

shown on rating plate.

 

 

2)

Restricted burner intake ports.

2) Clean burners free of debris or

 

 

 

 

 

insects.

 

 

3)

Restricted gas line.

3) Clean gas line or increase gas line

 

 

 

 

 

piping.

 

 

 

 

 

 

5)Sooting

1) Insufficient combustion air.

1)

Refer to installation instructions

 

 

 

 

 

regarding combustion air

 

 

 

 

 

requirements.

 

 

2)

Improper venting.

2)

Refer to installations instructions.

 

 

3) Severe yellow burner flames.

3)

See yellow flame section above.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 