Raypak 503 thru 2003 manual Heater, From Combustible, For Service, Side, Soft, Hard, Model, Amps

Models: 503 thru 2003 504 thru 2004

1 8
Download 8 pages 61.81 Kb
Page 5
Image 5
Heater

TOP VIEW

 

FRONT VIEW

FRONT VIEW

All components are contained inside the cabinet (except PRV), no external fans or valves to deal with.

 

 

Heater

From Combustible

For Service

 

 

 

 

 

Side

Surfaces (min.)

(recommended)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor*

 

0”

 

0”

 

 

 

CLEARANCES

Rear

 

12”

 

24”

 

 

 

Right Side

 

1”

 

1”

 

 

 

 

 

 

 

 

 

 

 

 

Left Side

 

1”

 

1”

 

 

 

 

 

Top

Indoor

0”

 

10”

 

 

 

 

 

 

Outdoor

Unobstructed

Unobstructed

 

 

 

 

 

Front

 

Open

 

24”

 

 

 

 

 

Vent Stack

Indoor

1”

 

1”

 

 

 

 

 

Vent Cap

Outdoor

12”

 

12”

 

 

 

 

 

*Do not install on carpeting

 

 

 

 

 

 

 

 

Note: Local codes may require increased clearances

 

 

 

 

 

 

 

MVB

 

 

Water Hardness

 

 

 

 

 

 

Soft

Medium

 

 

Hard

 

 

Model

 

 

 

 

 

HP

Amps

HP

Amps

HP

Amps

 

 

 

 

 

503/504

1/4

6

1/4

6

3/4

11

PUMP

 

 

 

 

 

 

 

 

 

753/754

1/4

6

1/2

7

3/4

11

 

1003/1104

1/4

6

1/2

7

1

14

 

 

 

 

 

 

 

 

 

 

 

1253

1/2

7

1

14

1

14

 

 

 

 

 

 

 

 

 

 

 

1503/1504

3/4

11

1

14

1

14

 

 

 

 

 

 

 

 

 

 

 

1753

1

14

1-1/2

15

1-1/2

15

 

 

2003/2004

1

14

1-1/2

15

1-1/2

15

 

 

 

 

 

 

 

 

 

 

Note: Current draw (Amps) is for pump only

Water hardness grains per gallon

 

Soft = 0-4 • Medium = 5-15 • Hard = 16-25

5

Page 5
Image 5
Raypak 503 thru 2003, 504 thru 2004 manual Heater, From Combustible, For Service, Side, Soft, Hard, Model, Amps