LOCATING YOUR U20/E21 FIREPLACE

INSTALLATION

LOCATING YOUR U20/E21 FIREPLACE

Due to high temperatures the Insert should be located out of traffic and away from furniture and draperies. Provide a minimum of 48" (1220mm) front clearance to the unit.

This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.

AB

F

C

D

E

This appliance is Listed for Alcove installations, maintain minimum Alcove clearances as follows, minimum ceiling height of 53-1/2", minimum width of 48" and a maximum depth of 36".

This unit is not approved for installation into a mobile home.

a) Cross Corner d) Island

b)Room Divider e) Flush with Wall

c) Flat on wall

f) Flat on Wall

 

Corner

FRAMING

1)The trim kit allows for 1/2" (13 mm) of finish facing material. The kit may be installed directly on and/or against standard combustible building materials.

2) Frame in the Zero Clearance box for the Kit with framing material. The framed opening for the assembled kit is 29-3/ 4" (756mm) high x 30.25" (768mm) wide x 16.5" (419mm) (17" (432mm) including drywall) deep. See diagram below.

3) For exterior walls, vapour barrier and insulate the Zero Clearance box to the same

degree as the rest of the house, or according to local installation codes.

4)The appliance may be

enclosed above the standoffs on the cabinet but the clearances stated on the b-vent chimney must be maintained.

U20/E21 Gas Insert Zero Clearance Kit

5

Page 5
Image 5