Installing the New Water Heater (cont’d)

Venting (cont’d)

WARNING

Be sure vent pipe is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation.

WARNING

Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.

Gas Piping

WARNING

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 10.5 in. water column (2.6kPa) for natural gas or 13 in. water column

WARNING

The appliance and its individual shutoff valve must be discon- nected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 12 pound per square inch (3.5kPa).

The appliance must be isolated from the gas supply piping sys- tem by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pres- sures equal to or less than 12 pound per square inch (3.5kPa).

Connecting the gas piping to the gas control valve of the water heater can be accomplished by either of the two methods shown.

SEDIMENT TRAP

A sediment trap shall be installed as close to the inlet of the water heater as practical at the time of water heater installation. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sedi- ment trap. If a tee fitting is used, it shall be installed in confor- mance with one of the methods of installation shown below.

GAS PIPING WITH FLEXIBLE CONNECTOR

(3.2kPa) for propane (L.P.) gas. The minimum inlet gas pressure listed on the rating plate is for the purpose of input adjustment.

WARNING

If the gas control valve is subjected to pressures exceeding 12 pound per square inch (3.5kPa), the damage to the gas con- trol valve could result in a fire or explosion from leaking gas.

WARNING

If the main gas line shutoff serving all gas appliances is used, also turn “OFF” the gas at each appliance. Leave all gas appli-

MANUAL SHUTOFF VALVE

GROUND JOINT UNION (Optional)

3MIN.

GAS SUPPLY PIPING

FLEXIBLE GAS CONNECTOR

LABELED AS COMPLYING

WITH ANSI STANDARDS

LOOP

GAS CONTROL VALVE

DRIP LEG (Sediment Trap)

CAP

ances shut off until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult the current edition of National Fuel Gas Code ANSI Z223.1, also referred to as NFPA 54 and the gas company con- cerning pipe size.

There shall be:

– A readily accessible manual shut off valve in the gas supply

line serving the water heater, and

GAS PIPING WITH ALL BLACK IRON PIPE

TO GAS CONTROL

GAS SUPPLY PIPING

MANUAL SHUTOFF

VALVE

BLACK PIPE

– A drip leg (sediment trap) ahead of the gas control valve to

help prevent dirt and foreign materials from entering the gas

control valve.

GROUND JOINT UNION

GAS CONTROL VALVE

– A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.

WARNING

Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases.

WARNING

The appliance and its gas connection must be leak test- ed before placing the appliance in operation.

3MIN.

 

DRIP LEG

 

 

(Sediment Trap)

 

 

 

 

 

 

CAP

 

 

 

WARNING

Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion. Before attaching the gas line be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a drip leg (sometimes called a sediment trap) shall be incorporated in the piping. The drip leg must be readily accessible. Install in accordance with the “Gas Piping” section. Refer to the current edition of the National Fuel Gas Code, ANSI Z223.1, also referred to as NFPA 54.

12

Page 12
Image 12
Reliance Water Heaters 184123-000 Venting cont’d, Gas Piping, Sediment Trap, GAS Piping with Flexible Connector