BELT-DRIVE AIRFLOW PERFORMANCE

 

 

Model

 

RJNA-A060 [17.58 kW]—Heat Pump (13 SEER)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

Voltage

208/230-460—3 Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure—Inches of Water [kPa]

 

 

 

 

 

 

 

 

 

 

 

 

CFM [L/s]

0.1 [.02]

 

0.2 [.05]

0.3 [.07]

0.4 [.10]

0.5 [.12]

0.6 [.15]

0.7 [.17]

0.8 [.20]

0.9 [.22]

1.0 [.25]

1.1 [.27]

1.2 [.30]

1.3 [.32]

1.4 [.35]

1.5 [.37]

 

 

RPM

 

W

 

RPM

W

RPM

 

W

RPM

W

RPM

W

RPM

 

W

RPM

W

RPM

W

RPM

W

RPM

W

RPM

W

RPM

W

RPM

W

RPM

W

RPM

W

1400

[661]

 

 

780

 

370

815

385

875

425

930

 

460

970

490

1030

540

1065

570

1105

595

1150

615

1195

645

1235

660

1300

705

1340

745

1500

[708]

 

 

795

 

405

840

415

895

440

945

 

500

995

540

1045

595

1080

615

1135

650

1165

675

1215

700

1255

735

1320

775

1355

805

1600

[755]

 

 

780

390

805

 

425

870

470

915

510

965

 

560

1015

600

1060

640

1105

680

1145

705

1180

730

1225

750

1275

790

1340

840

1365

880

1700

[802]

 

 

795

450

840

 

490

895

530

940

570

990

 

605

1035

640

1075

680

1120

725

1160

755

1200

790

1245

815

1300

855

1355

905

1375

940

1800

[850]

780

 

455

 

815

470

870

 

540

915

540

965

675

1010

 

660

1055

710

1100

760

1140

785

1175

810

1225

850

1260

880

1320

930

1365

985

1390

1020

1900

[897]

800

 

485

 

850

530

895

 

590

945

640

995

675

1035

 

720

1070

775

1120

810

1160

850

1200

890

1245

915

1290

960

1335

1000

1375

1050

1405

1100

2000

[944]

830

 

550

 

880

605

930

 

655

970

700

1015

730

1055

 

790

1105

830

1145

875

1180

910

1225

950

1260

980

1320

1035

1350

1075

1385

1120

2100

[991]

860

 

615

 

915

655

955

 

705

1005

760

1040

820

1090

 

870

1130

910

1170

950

1210

995

1250

1020

1290

1060

1335

1100

1370

1150

1400

1200

2200 [1038]

895

 

680

 

945

735

995

 

780

1030

830

1060

880

1120

 

940

1155

980

1195

1020

1240

1055

1275

1100

1320

1140

1360

1180

1385

1225

2300 [1085]

940

 

755

 

975

795

1015

 

830

1065

910

1100

965

1150

 

1025

1180

1050

1225

1095

1265

1125

1310

1175

1350

1230

1375

1260

1405

1320

2400 [1133]

970

 

825

 

1015

880

1040

 

925

1100

1005

1145

1055

1175

 

1085

1225

1140

1260

1175

1300

1210

1340

1255

1370

1315

1400

1375

NOTE: L-Drive left of bold line, M-Drive right of bold line.

Drive Package

 

 

 

L

 

 

 

 

 

 

M

 

 

 

Motor H.P. [w]

 

 

 

3/4 [559]

 

 

 

 

 

 

1 [746]

 

 

 

Blower Sheave

 

 

6.4 Pitch Diameter

 

 

 

 

6.4 Pitch Diameter

 

 

Motor Sheave

 

Adjustable 2.8-3.8 Pitch Diameter

 

 

Adjustable 3.4-4.4 Pitch Diameter

 

Turns Open

0

1

2

3

4

5

6

0

1

2

3

4

5

6

RPM

1095

1040

995

940

890

835

780

1405

1360

1305

1250

1195

1145

1095

Factory sheave settings are shown in bold print.

21

COMPONENT AIR RESISTANCE

 

 

 

 

Standard Indoor Airflow—CFM [L/s]

 

 

Component

1000 [472]

1200 [566]

1400 [661]

 

1600 [755]

1800 [850]

2000 [944]

2200 [1038]

2400 [1133]

 

 

 

 

 

Resistance—Inches Water [kPa]

 

 

Wet Coil

.035

.040

.060

 

.070

.085

.100

.110

.120

Downflow

.055

.060

.066

 

.072

.080

.086

.093

.100

 

 

 

 

 

 

 

 

 

 

Economizer

.05

.06

.07

 

.08

.09

.10

.11

.12

R.A. Damper

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Performance shown with dry coil, standard 1" [25.4 mm] filters & side discharge. Add component resistance to determine total E.S.P.

2.Standard CFM @ .075 lbs./cu. ft.

3.Motor efficiency = 80%

4.BHP = Watts x Motor Eff.

746

[ ] Designates Metric Conversions

SERIES -RJNA—PERFORMANCE AIRFLOW