ELECTRICAL
ELECTRICAL DATA – RJNA SERIES
Evaporator Fan Condenser Motor Compressor Motor Unit Information
|
| |||||||||||||
Unit Operating |
| |||||||||||||
Voltage Range |
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Minimum Circuit | 22/22 | 21/21 | 22/22 | 11 | 11 | 11 | 30/30 | 32/32 | 28/28 | 28/28 | 14 | 14 | 46/46 |
|
Ampacity |
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Minimum Overcurrent | 25/25 | 25/25 | 25/25 | 15 | 15 | 15 | 35/35 | 40/40 | 35/35 | 35/35 | 20 | 20 | 60/60 |
|
Protection Device Size |
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Maximum Overcurrent | 30/30 | 30/30 | 30/30 | 15 | 15 | 15 | 45/45 | 45/45 | 45/45 | 45/45 | 20 | 20 | 60/60 |
|
Protection Device Size |
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
No. | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
|
Volts | 208/230 | 208/230 | 208/230 | 460 | 460 | 460 | 208/230 | 208/230 | 208/230 | 208/230 | 460 | 460 | 208/230 |
|
Phase | 3 | 3 | 3 | 3 | 3 | 3 | 1 | 3 | 3 | 3 | 3 | 3 | 1 |
|
HP | 3.5 | 3.5 | 3.5 | 3.5 | 3.5 | 3.5 | 3.5 | 5 | 5 | 5 | 5 | 5 | 5 |
|
RPM | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 | 3450 |
|
Amps (RLA) | 12.4/12.4 | 12.4/12.4 | 12.4/12.4 | 6.4 | 6.4 | 6.4 | 18.3/18.3 | 17.3/17.3 | 17.3/17.3 | 17.3/17.3 | 8.2 | 8.2 | 28.8/28.8 |
|
Amps (LRA) | 88/88 | 88/88 | 88/88 | 44 | 44 | 44 | 109/109 | 123/123 | 123/123 | 123/123 | 62 | 62 | 148/148 |
|
No. | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
|
Volts | 208/230 | 208/230 | 208/230 | 460 | 460 | 460 | 208/230 | 208/230 | 208/230 | 208/230 | 460 | 460 | 208/230 |
|
Phase | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
|
HP | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 | 1/3 |
|
Amps (FLA) | 2.2 | 2.2 | 2.2 | 1 | 1 | 1 | 2.2 | 2.2 | 2.2 | 2.2 | 1 | 1 | 2.2 |
|
Amps (LRA) | 4.7 | 4.7 | 4.7 | 2.4 | 2.4 | 2.4 | 4.7 | 4.7 | 4.7 | 4.7 | 2.4 | 2.4 | 4.7 |
|
No. | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
|
Volts | 208/230 | 208/230 | 208/230 | 460 | 460 | 460 | 208/230 | 208/230 | 208/230 | 208/230 | 460 | 460 | 208/230 |
|
Phase | 1 | 3 | 3 | 1 | 3 | 3 | 1 | 1 | 3 | 3 | 3 | 3 | 1 |
|
HP | 1/2 | 1/2 | 3/4 | 1/2 | 1/2 | 3/4 | 1/2 | 1 | 3/4 | 1 | 3/4 | 1 | 1 |
|
Amps (FLA) | 2.7 | 2.2 | 3.2 | 1.5 | 1.1 | 1.6 | 2.7 | 7.6 | 3.2 | 3.8 | 1.6 | 1.9 | 7.6 |
|
Amps (LRA) | 6.5 | 10.6 | 16.8 | 3.6 | 5.3 | 8.4 | 6.5 | 0 | 16.8 | 24 | 8.4 | 12 | 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.Horsepower Per Compressor.
2.Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
23