Rheem RSNA-B Series GROSS SYSTEMS PERFORMANCE DATA-RSNA-B036, Systems Performance-Rsna-Bseries

Models: RSNA-B Series

1 40
Download 40 pages 21.43 Kb
Page 12
Image 12
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036

SYSTEMS PERFORMANCE—RSNA-B SERIES

GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE

 

71°F [21.7°C]

 

 

67°F [19.4°C]

 

 

63°F [17.2°C]

 

CFM [L/s]

1320 [623]

1200 [566]

1020 [481]

1320 [623]

1200 [566]

1020 [481]

1320 [623]

1200 [566]

1020 [481]

DR

.21

.20

.17

.21

.20

.17

.21

.20

.17

 

75

Total BTUH [kW]

44.4 [13.01]

43.6 [12.78]

42.4 [12.43]

41.3 [12.10]

40.6 [11.90]

39.5 [11.58]

39.6 [11.61]

38.9 [11.40]

37.8 [11.08]

 

Sens BTUH [kW]

25.5

[7.47]

24.4

[7.15]

22.7

[6.65]

30.4

[8.91]

29.1

[8.53]

27.0

[7.91]

31.4

[9.20]

30.0

[8.79]

27.9

[8.18]

 

[23.9]

O

Power

 

2.2

 

2.1

 

2.1

 

2.1

 

2.1

 

2.1

 

2.1

 

2.1

 

2.1

 

Total BTUH [kW]

43.6 [12.78]

42.8 [12.54]

41.7 [12.22]

40.5 [11.87]

39.8 [11.66]

38.7 [11.34]

38.7 [11.34]

38.0 [11.14]

37.0 [10.84]

U

80

T

Sens BTUH [kW]

25.0

[7.33]

23.9

[7.00]

22.2

[6.51]

29.9

[8.76]

28.6

[8.38]

26.6

[7.80]

30.8

[9.03]

29.5

[8.65]

27.4

[8.03]

[26.7]

D

Power

 

2.3

 

2.3

 

2.2

 

2.3

 

2.3

 

2.2

 

2.3

 

2.3

 

2.2

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

85

Total BTUH [kW]

42.8 [12.54]

42.1 [12.34]

40.9 [11.99]

39.7 [11.63]

39.0 [11.43]

38.0 [11.14]

38.0 [11.14]

37.3 [10.93]

36.3 [10.64]

R

Sens BTUH [kW]

24.5

[7.18]

23.4

[6.86]

21.8

[6.39]

29.4

[8.62]

28.1

[8.24]

26.1

[7.65]

30.3

[8.88]

29.0

[8.50]

27.0

[7.91]

 

[29.4]

D

Power

 

2.4

 

2.4

 

2.4

 

2.4

 

2.4

 

2.4

 

2.4

 

2.4

 

2.4

R

90

Total BTUH [kW]

42.0 [12.31]

41.3 [12.10]

40.2 [11.78]

38.9 [11.40]

38.3 [11.22]

37.2 [10.90]

37.2 [10.90]

36.5 [10.70]

35.5 [10.40]

Y

Sens BTUH [kW]

24.0

[7.03]

22.9

[6.71]

21.3

[6.24]

28.9

[8.47]

27.6

[8.09]

25.7

[7.53]

29.9

[8.76]

28.5

[8.35]

26.5

[7.77]

 

[32.2]

B

Power

 

2.6

 

2.5

 

2.5

 

2.6

 

2.5

 

2.5

 

2.5

 

2.5

 

2.5

U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total BTUH [kW]

41.1 [12.05]

40.4 [11.84]

39.3 [11.52]

38.0 [11.14]

37.4 [10.96]

36.3 [10.64]

36.3 [10.64]

35.6 [10.43]

34.7 [10.17]

L

95

B

Sens BTUH [kW]

23.5

[6.89]

22.4

[6.56]

20.9

[6.13]

28.4

[8.32]

27.1

[7.94]

25.2

[7.39]

29.3

[8.59]

28.0

[8.21]

26.0

[7.62]

[35]

 

Power

 

2.7

 

2.7

 

2.6

 

2.7

 

2.7

 

2.6

 

2.7

 

2.7

 

2.6

T

 

 

 

 

 

 

 

 

 

 

E

100

Total BTUH [kW]

40.0 [11.72]

39.3 [11.52]

38.2 [11.20]

36.9 [10.81]

36.3 [10.64]

35.3 [10.35]

35.2 [10.32]

34.5 [10.11]

33.6

[9.85]

M

Sens BTUH [kW]

22.8

[6.68]

21.8

[6.39]

20.3

[5.95]

27.7

[8.12]

26.5

[7.77]

24.6

[7.21]

28.7

[8.41]

27.4

[8.03]

25.5

[7.47]

P

[37.8]

E

 

Power

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

R

105

Total BTUH [kW]

38.6 [11.31]

37.9 [11.11]

36.9 [10.81]

35.5 [10.40]

34.9 [10.23]

33.9

[9.94]

33.8

[9.91]

33.2

[9.73]

32.3

[9.47]

A

Sens BTUH [kW]

22.1

[6.48]

21.1

[6.18]

19.6

[5.74]

26.9

[7.88]

25.7

[7.53]

23.9

[7.00]

27.9

[8.18]

26.6

[7.80]

24.8

[7.27]

T

[40.6]

U

Power

 

3.0

 

3.0

 

2.9

 

3.0

 

2.9

 

2.9

 

3.0

 

2.9

 

2.9

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total BTUH [kW]

36.9 [10.81]

36.2 [10.61]

35.2 [10.32]

33.8

[9.91]

33.1

[9.70]

32.2

[9.44]

32.0

[9.38]

31.4

[9.20]

30.6

[8.97]

E

110

Sens BTUH [kW]

21.1

[6.18]

20.1

[5.89]

18.7

[5.48]

26.0

[7.62]

24.8

[7.27]

23.1

[6.77]

26.9

[7.88]

25.7

[7.53]

23.9

[7.00]

°F

[43.3]

Power

 

3.1

 

3.1

 

3.1

 

3.1

 

3.1

 

3.0

 

3.1

 

3.1

 

3.0

[°C]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115

Total BTUH [kW]

34.6 [10.14]

34.0

[9.96]

33.1

[9.70]

31.5

[9.23]

30.9

[9.06]

30.1

[8.82]

29.7

[8.70]

29.2

[8.56]

28.4

[8.32]

 

 

Sens BTUH [kW]

19.9

[5.83]

19.0

[5.57]

17.7

[5.19]

24.8

[7.27]

23.7

[6.95]

22.0

[6.45]

25.7

[7.53]

24.6

[7.21]

22.9

[6.71]

 

[46.1]

 

Power

 

3.3

 

3.2

 

3.2

 

3.2

 

3.2

 

3.2

 

3.2

 

3.2

 

3.2

GROSS SYSTEMS PERFORMANCE DATA—RSNA-B042

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE

 

71°F [21.7°C]

 

 

67°F [19.4°C]

 

 

63°F [17.2°C]

 

CFM [L/s]

1490 [703]

1350 [637]

1150 [543]

1490 [703]

1350 [637]

1150 [543]

1490 [703]

1350 [637]

1150 [543]

DR

.24

.23

.21

.24

.23

.21

.24

.23

.21

 

75

Total BTUH [kW]

51.1 [14.98]

50.2 [14.71]

48.8 [14.30]

47.7 [13.98]

46.9 [13.75]

45.6 [13.36]

45.2 [13.25]

44.3 [12.98]

43.1 [12.63]

 

Sens BTUH [kW]

28.1

[8.24]

26.9

[7.88]

25.0

[7.33]

33.4

[9.79]

31.9

[9.35]

29.7

[8.70]

37.9 [11.11]

36.2 [10.61]

33.6

[9.85]

 

[23.9]

O

Power

 

2.6

 

2.6

 

2.5

 

2.5

 

2.5

 

2.5

 

2.5

 

2.5

 

2.5

 

Total BTUH [kW]

50.1 [14.68]

49.2 [14.42]

47.8 [14.01]

46.7 [13.69]

45.9 [13.45]

44.6 [13.07]

44.1 [12.92]

43.3 [12.69]

42.2 [12.37]

U

80

T

Sens BTUH [kW]

27.9

[8.18]

26.7

[7.83]

24.8

[7.27]

33.2

[9.73]

31.7

[9.29]

29.5

[8.65]

37.6 [11.02]

36.0 [10.55]

33.5

[9.82]

[26.7]

D

Power

 

2.7

 

2.7

 

2.7

 

2.7

 

2.7

 

2.6

 

2.7

 

2.7

 

2.6

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

85

Total BTUH [kW]

49.0 [14.36]

48.1 [14.10]

46.8 [13.72]

45.6 [13.36]

44.8 [13.13]

43.6 [12.78]

43.1 [12.63]

42.3 [12.40]

41.1 [12.05]

R

Sens BTUH [kW]

27.5

[8.06]

26.3

[7.71]

24.5

[7.18]

32.8

[9.61]

31.3

[9.17]

29.1

[8.53]

37.2 [10.90]

35.6 [10.43]

33.1

[9.70]

 

[29.4]

D

Power

 

2.9

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

 

2.8

R

90

Total BTUH [kW]

47.9 [14.04]

47.0 [13.77]

45.8 [13.42]

44.5 [13.04]

43.7 [12.81]

42.5 [12.46]

42.0 [12.31]

41.2 [12.07]

40.1 [11.75]

Y

Sens BTUH [kW]

27.0

[7.91]

25.8

[7.56]

24.0

[7.03]

32.2

[9.44]

30.8

[9.03]

28.6

[8.38]

36.7 [10.76]

35.0 [10.26]

32.6

[9.55]

 

[32.2]

B

Power

 

3.0

 

3.0

 

2.9

 

3.0

 

3.0

 

2.9

 

3.0

 

2.9

 

2.9

U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total BTUH [kW]

46.8 [13.72]

45.9 [13.45]

44.7 [13.10]

43.4 [12.72]

42.6 [12.48]

41.4 [12.13]

40.8 [11.96]

40.1 [11.75]

39.0 [11.43]

L

95

B

Sens BTUH [kW]

26.3

[7.71]

25.1

[7.36]

23.4

[6.86]

31.5

[9.23]

30.1

[8.82]

28.0

[8.21]

36.0 [10.55]

34.4 [10.08]

32.0

[9.38]

[35]

 

Power

 

3.2

 

3.1

 

3.1

 

3.1

 

3.1

 

3.1

 

3.1

 

3.1

 

3.0

T

 

 

 

 

 

 

 

 

 

 

 

Total BTUH [kW]

45.6 [13.36]

44.8 [13.13]

43.6 [12.78]

42.2 [12.37]

41.5 [12.16]

40.4 [11.84]

39.7 [11.63]

39.0 [11.43]

37.9 [11.11]

E

100

M

Sens BTUH [kW]

25.6

[7.50]

24.4

[7.15]

22.7

[6.65]

30.8

[9.03]

29.4

[8.62]

27.4

[8.03]

35.3 [10.35]

33.7

[9.88]

31.3

[9.17]

P

[37.8]

E

 

Power

 

3.3

 

3.3

 

3.2

 

3.3

 

3.2

 

3.2

 

3.3

 

3.2

 

3.2

R

105

Total BTUH [kW]

44.5 [13.04]

43.7 [12.81]

42.5 [12.46]

41.1 [12.05]

40.4 [11.84]

39.3 [11.52]

38.6 [11.31]

37.9 [11.11]

36.8 [10.79]

A

Sens BTUH [kW]

24.8

[7.27]

23.7

[6.95]

22.1

[6.48]

30.1

[8.82]

28.7

[8.41]

26.7

[7.83]

34.5 [10.11]

33.0

[9.67]

30.7

[9.00]

T

[40.6]

U

Power

 

3.4

 

3.4

 

3.4

 

3.4

 

3.4

 

3.3

 

3.4

 

3.4

 

3.3

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total BTUH [kW]

43.4 [12.72]

42.6 [12.48]

41.5 [12.16]

40.0 [11.72]

39.3 [11.52]

38.2 [11.20]

37.5 [10.99]

36.8 [10.79]

35.8 [10.49]

E

110

Sens BTUH [kW]

24.2

[7.09]

23.1

[6.77]

21.5

[6.30]

29.4

[8.62]

28.1

[8.24]

26.1

[7.65]

33.9

[9.94]

32.4

[9.50]

30.1

[8.82]

°F

[43.3]

Power

 

3.6

 

3.6

 

3.5

 

3.6

 

3.5

 

3.5

 

3.5

 

3.5

 

3.5

[°C]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115

Total BTUH [kW]

42.3 [12.40]

41.6 [12.19]

40.4 [11.84]

39.0 [11.43]

38.3 [11.22]

37.2 [10.90]

36.4 [10.67]

35.7 [10.46]

34.8 [10.20]

 

 

Sens BTUH [kW]

23.6

[6.92]

22.5

[6.59]

21.0

[6.15]

28.8

[8.44]

27.5

[8.06]

25.6

[7.50]

33.3

[9.76]

31.8

[9.32]

29.6

[8.67]

 

[46.1]

 

Power

 

3.7

 

3.7

 

3.7

 

3.7

 

3.7

 

3.6

 

3.7

 

3.7

 

3.6

DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb

Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input

NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

[ ] Designates Metric Conversions

12

Page 12
Image 12
Rheem RSNA-B Series manual GROSS SYSTEMS PERFORMANCE DATA-RSNA-B036, GROSS SYSTEMS PERFORMANCE DATA-RSNA-B042

FAQ

What is the DR in the performance data table?

DR stands for Depression Ratio and is a measure of the cooling capacity relative to the dry bulb temperature of the entering air.

How can I adjust the sensible capacity if the entering air dry bulb is not 80F (27C)?

You can adjust the sensible capacity by adding 1.10 x CFM x 1DR x dbE80 to the capacity from the table.

What language is the performance data presented in?

The performance data is presented in English and includes metric conversions for easy reference.