ELECTRICAL DATA—RSNA-B SERIES

ELECTRICAL DATA—RSNA-B SERIES

ELECTRICAL DATA – RSNA-B SERIES

 

 

-B024JK

-B030JK

-B036CK

-B036JK

-B042CK

-B042JK

-B048CK

-B048JK

-B060CK

-B060JK

 

Unit Operating

187-253

187-253

187-253

187-253

187-253

187-253

187-253

187-253

187-253

187-253

Information

Voltage Range

 

 

 

 

 

 

 

 

 

 

Minimum Overcurrent

16/16

22/22

16/16

22/22

18/18

26/26

22/22

32/32

33/33

43/43

 

Minimum Circuit Ampacity

Unit

Protection Device Size

20/20

25/25

20/20

30/30

20/20

30/30

25/25

40/40

40/40

50/50

 

 

 

 

 

 

 

 

 

 

Maximum Overcurrent

25/25

35/35

25/25

35/35

25/25

40/40

30/30

50/50

50/50

60/60

 

 

Protection Device Size

 

 

 

 

 

 

 

 

 

 

 

Motor

No.

1

1

1

1

1

1

1

1

1

1

Volts

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

 

Compressor

Phase

1

1

3

1

3

1

3

1

3

1

HP

2 1/6

2 2/3

3 1/3

3 1/3

3 1/2

3 1/2

4

4

5

5

 

 

RPM

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

 

Amps (RLA)

10.4/10.4

14.1/14.1

9.6/9.6

14.4/14.4

10.3/10.3

16.5/16.5

12.2/12.2

20.2/20.2

17.3/17.3

25/25

 

Amps (LRA)

54/54

68/68

88/88

77/77

77/77

95/95

80.8/80.8

137/137

123/123

148/148

Motor

No.

1

1

1

1

1

1

1

1

1

1

Volts

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

 

Condenser

Phase

1

1

1

1

1

1

1

1

1

1

HP

1/5

1/5

1/5

1/5

1/3

1/3

1/3

1/3

1/3

1/3

 

 

Amps (FLA)

1.3

1.3

1.3

1.3

2

2

2

2

2

2

 

Amps (LRA)

2.3

2.3

2.3

2.3

3.9

3.9

3.9

3.9

3.9

3.9

Fan

No.

1

1

1

1

1

1

1

1

1

1

Volts

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

Evaporator

Phase

1

1

1

1

1

1

1

1

1

1

 

 

HP

1/4

1/2

1/2

1/2

1/2

1/2

3/4

3/4

1

1

 

Amps (FLA)

1.3

2.4

2.4

2.4

2.4

2.4

4.4

4.4

9.1

9.1

 

Amps (LRA)

2.3

5.1

5.1

5.1

5.1

5.1

9.5

9.5

0

0

1.Horsepower Per Compressor.

2.Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.

Copper Wire Size—AWG (1% Voltage Drop)

SUPPLY WIRE LENGTH-FEET

300

4

3

2

2

1

1/0

1/0

2/0

2/0

3/0

3/0

3/0

4/0

4/0

4/0

4/0

250

250

250

250

300

300

300

250

4

4

3

3

2

1

1

1/0

1/0

2/0

2/0

2/0

3/0

3/0

3/0

4/0

4/0

4/0

4/0

4/0

250

250

250

200

6

4

4

4

3

2

2

1

1

1/0

1/0

1/0

2/0

2/0

2/0

3/0

3/0

3/0

3/0

3/0

4/0

4/0

4/0

150

8

6

6

4

4

4

3

3

2

2

1

1

1/0

1/0

1/0

1/0

2/0

2/0

2/0

2/0

2/0

3/0

3/0

100

10

8

8

6

6

6

4

4

4

3

3

2

2

2

1

1

1

1

1

1/0

1/0

1/0

1/0

50

14

12

10

10

8

8

6

6

6

4

4

4

3

3

3

2

2

2

2

2

1

1

1

 

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT AMPACITY

 

 

 

 

 

 

 

 

 

Notes: 1. Wire size based on 60°C. type copper conductors below 100 ampacity.

2. Wire size based on 75°C. type copper conductors for 100 ampacity and above.

[ ] Designates Metric Conversions

 

16

Page 16
Image 16
Rheem RSNA-B Series Electrical Data-Rsna-Bseries, Electrical Data - Rsna-Bseries, Copper Wire Size-AWG 1% Voltage Drop

FAQ

What are the electrical specifications for Rheem RSNA-B Series?

The electrical data for RSNA-B Series includes voltage range, minimum overcurrent, maximum overcurrent, compressor horsepower, motor amp draw, and wire size recommendations for different supply wire lengths.

How to determine total amps for RSNA-B Series?

You can determine total amps by multiplying the value of amp draw per motor by the number of motors specified in the electrical data.

What are the wire size recommendations for RSNA-B Series based on circuit ampacity?

The wire size recommendations for RSNA-B Series are based on the circuit ampacity and are provided for different supply wire lengths in the electrical data.