Roberts Gorden BH-60, BH-40 Model, Tubing Length, Core Packages, Minimum, Standard, Aluminized

Models: BH-80 BH-200 BH-140 BH-100 BH-115 BH-175 BH-150 BH-40 BH-60

1 20
Download 20 pages 37.5 Kb
Page 18
Image 18
Tubing Length

BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Table 3: BH-Series Component Package Guide

Model

Tubing Length

Core Packages

 

 

 

Minimum

Standard

Aluminized

 

 

 

 

 

BH-40

10' (3 m)

-

CP10ALUM

 

 

 

 

BH-60

20' (6 m)

CP20HRS

CP20ALUM

 

 

 

 

BH-80

20' (6 m)

CP20HRS

CP20ALUM

 

 

 

 

BH-100

30' (9 m)

CP30HRS

CP30ALUM

 

 

 

 

BH-115

30' (9 m)

CP30HRS

CP30ALUM

 

 

 

 

BH-125

40' (12 m)

CP40HRS

CP40ALUM

 

 

 

 

BH-140

40' (12 m)

CP40HRS

CP40ALUM

 

 

 

 

BH-150

50' (15 m)

CP30HRS + EXP20HRS

CP30ALUM + EXP20ALUM

 

 

 

 

BH-175

50' (15 m)

CP30HRS + EXP20HRS

CP30ALUM + EXP20ALUM

 

 

 

 

BH-200

60' (18 m)

CP30HRS + EXP30HRS

CP30ALUM + EXP30ALUM

 

 

 

 

Additional tubing length may be added to heater. Tubing must be heat-treated, aluminized or porcelain coated. Any additional tubing lengths are considered as vent length for length determination. Maximum venting length for minimum heater length is 45' (13.7 m) total.

12

Page 18
Image 18
Roberts Gorden BH-60, BH-40, BH-150, BH-175, BH-115, BH-100 Model, Tubing Length, Core Packages, Minimum, Standard, Aluminized