SECTION 6: RADIANT TUBE AND TAILPIPE
4.Select pump model series for total system flow units:
5.See Page 14, Table 2 for altitudes greater than 2000'.
6.For each branch, add the length of radiant tube
after each heater:
Burner | Radiant Tube Length | |||
After Each Burner | ||||
| ||||
1 | + | |||
2 |
|
| + | |
| ||||
3 |
|
| + | |
| ||||
4 |
|
| + | |
| ||||
5 |
|
| + | |
| ||||
6 |
|
| + | |
| ||||
|
|
|
|
Total Radiant Tube
Length in Branch =
Repeat this calculation for each branch in the system.
7.Divide the total radiant tube length in the branch by the number of burners in the branch to get the average radiant length per burner.
Average Radiant
Length Per Burner =
Repeat this calculation for each branch in the system.
8.Using the average radiant length per burner (Calculated in Step 7) See Page 17, Table 4 to select the allowable tailpipe lengths per flow unit.
Table 4: Allowable Tailpipe Lengths
|
|
|
| Burner Model |
|
| ||
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
Radiant Tube Length (average distance between burners) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Minimum (ft) | 10 | 12.5 | 20 |
| 20 | 20 | 30 | 35 |
|
|
|
|
|
|
|
|
|
Recommended (ft) | 15 | 20 | 25 |
| 30 | 30 | 40 | 50 |
|
|
|
|
|
|
|
|
|
Maximum (ft) | 20 | 25 | 35 |
| 45 | 50 | 60 | 70 |
|
|
|
|
|
|
|
|
|
Tailpipe length per flow unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Minimum (ft)* | 1.2 | 1.2 | 1.2 |
| 1.2 | 1.2 | 1.2 | 1.2 |
|
|
|
|
|
|
|
|
|
Recommended (ft) | 1.5 | 1.5 | 1.5 |
| 1.5 | 1.5 | 1.5 | 1.5 |
|
|
|
|
|
|
|
|
|
Maximum (ft) | 2.5 | 2.5 | 2.5 |
| 2.5 | 2.5 | 2.5 | 2.5 |
|
|
|
|
|
|
|
|
|
Maximum (ft) for | 1.7 | 1.7 | 1.7 |
| 1.7 | 1.7 | 1.7 | 1.7 |
|
|
|
|
|
|
|
|
|
*Minimum tailpipe lengths can only be used if radiant tube length is recommended or greater.
17