SECTION 11: CRV-SERIES EQUIPMENT SPECIFICATIONS
The total heating system supplied shall be design cer- tified by the CSA International per American National Standard ANSI Z83.20/CSA 2.34 (latest edition).
11.1 Burner and Burner Controls
11.1.1Burners shall be designed to operate simulta- neously in series without adverse effects from com- bustion gases from upstream burners.
11.1.2Burners shall be capable of firing on:
Natural Gas, or LP Gas.
11.1.3Burners shall be supplied to fire at any one of the input firing rates as specified:
When using ROBERTS GORDON® ULTRAVAC™ con- trols, burner rates will modulate between 60% and 100% rated input
11.1.4The design of burners supplied shall provide for maintaining a constant proportion of fuel gas to fil- tered combustion air. These conditions are met for burners in which the pressure of both the fuel gas and the combustion air are introduced at zero (atmo- spheric) pressure and the flow of each is established by a vacuum on the downstream side of the flow metering orifices.
11.1.5To assure a high degree of
1.Main valve fails in open position.
2.Vacuum pump motor fails to operate.
3.Power fails.
11.1.6To further assure a high degree of safety, the system will be under negative pressure at all times during operation to preclude the possibility of the escape of combustion gases inside the building.
11.1.7The burner control assembly will include a zero regulator.
11.1.8All burners shall be
11.2Equipment 11.2.1 Burner
Each burner assembly shall consist of
11.2.2 Pump
The pump model supplied will vary with the capacity of the system. See the pump technical specification sheet or the installation, operation and service manual for product description and specification.
The pump shall be acoustically isolated from the sys- tem with a flexible connector with temperature rating of 350°F minimum. The motor in the vacuum pump shall be secured with rubber mounts for acoustical isolation.
11.2.3 Heat Exchanger
Radiant tubing (between burners and 10’ - 70’ down- stream of last burner) shall be of 4" O.D. steel or heat treated aluminized tubing.
As an option, the balance of the tubing shall be 4" O.D. steel tubing with an internal and external coating of
All heat exchanger (tubing) connections shall be made with stainless steel coupling assemblies. Standard couplings will be used in radiant sections. Lined cou- plings will be used in tailpipe sections.
11.2.4 Outside Air
When specified, in contaminated environments, the system shall be capable of supplying air from the out- side to each burner and end vent for the support of combustion.
32