EXAMPLE 3: B-10 Radiant Tube vs. Tailpipe Length
For a
From Table 4, we can use between 1.2' per flow unit and 2.5' per flow unit when the average radiant length per
Tailpipe length range for a
Table 5: Operating Characteristics; Condensing or
|
| Tailpipe Length per Flow Unit |
| |||
|
|
|
|
|
|
|
| Minimum |
| Recommended | 1.7 ft/flow unit |
| Maximum |
|
|
|
|
|
|
|
Radiant Tube Length (average distance between burners) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Minimum | N/A |
| NC | Borderline |
| C |
|
|
|
|
|
|
|
Recommended | NC |
| Borderline | C |
| C |
|
|
|
|
|
|
|
Maximum | Borderline |
| C | C |
| C |
|
|
|
|
|
|
|
N/A=Not Allowed NC=Non Condensing C=Condensing
6.5 Tailpipe Design Method
Given the overall length of tailpipe for the system, the following section provides the method for ensuring the design will function correctly.
Total tailpipe |
| ' (includes 1 elbow / 50'). |
6.5.1 Rule of Thumb Unshared Calculations
Total tailpipe - 10' | = Optimum unshared |
| tailpipe per branch |
Number of branches |
the section of tailpipe.
If flow units entering a shared tailpipe system exceed 90% of pump capacity, the length of 4" diameter tailpipe must not exceed 20'.
System with EP-300 Series Pump
For shared tailpipe up to 115 flow units, 4" diameter tailpipe can be used. See Page 14, Figure 15 for max- imum permissible length of tailpipe for the number of flow units entering the section of tailpipe.
Select a pump discharge location and plan the route of the tailpipe. For example system layouts See Page 21, Figure 18 through Page 25, Figure 26 for different pump and system efficiency requirements. If these lay- outs are not suitable, it is necessary to customize the layout for the
For multiple branch systems, always plan to connect the unshared tailpipe together as close to the pump as possible for better system efficiency.
6.5.2 Shared Tailpipe Calculation
System with EP-100 or EP-200 Series Pump
Shared tailpipe greater than 115 flow units use 6" diameter tube. Note that all tailpipe lengths for the pur- poses of calculation are expressed in terms of 4" diameter tube.
Effective length: 10' (3 m) of 6" (15 cm) diameter tube = 13' (4 m) of 4" diameter tube.
6.5.3 To Calculate the Total System Tailpipe
Total unshared tailpipe + shared 4" branch tailpipe + effective length of shared 6".
6.5.4 To Check Performance Criteria
Total system tailpipe | = Tailpipe ft/flow unit | |
Total flow units | ||
|
See Page 14, Figure 15 for maximum permissible
length of tailpipe for the number of flow units entering Compare the results to Page 17, Table 4 and Page 18,
18