11

English

HIGH Sensitivity – should be used when the connected equipment is sensitive to momentary low voltage or brief power fluctuations. In HIGH Sensitivity the unit is very sensitive to voltage distortion and is, therefore, more likely to switch back and forth to battery power than it would under a MEDIUM or LOW sensitivity setting.

MEDIUM Sensitivity – is the default setting suitable for most situations.

LOW Sensitivity – should be used when the RLC-1080 frequently switches to the internal battery power source even though the input voltage appears normal. Example: If the unit goes ON BATTERY when your power amplifier is turned on.

����������������

������������������

DISPLAY DIMMER Setting

This lets you set the brightness level of the VFD to HIGH, LOW, or OFF. Use the SETUP button to advance to the Display Dimmer screen. Once the display is shown, pressing the Up/Down Arrow buttons changes the brightness of the display. Once the Display brightness is at the desired level, press the SETUP push button to store the setting.

�������������������

������������������

Note: Even when the display dimmer is set to OFF, the screen will turn back on momentarily when there is a significant change in system status, such as a power outage or a low bat- tery condition.

LED DIMMER Setting

This lets you set a brightness level of the front-panel light emitting diode (LED) indicators to HIGH,

LOW, or OFF. Use the SETUP button to advance to the LED DIMMER screen (not shown). Once the display is shown, press the Up/Down Arrow buttons to set the brightness of the LEDs. Once the LED brightness is at the desired level, press the SETUP push button to store the setting.

GO TO BATTERY IF > XXXV Setting

This lets you set a high voltage threshold for the unit. If the power input voltage goes up to the level set on this display screen, the RLC-1080 switches to Internal Battery power. The input voltage when this happens can be set from 134 to 144 volts.

�������������������

������������������

GO TO BATTERY IF < XXXV Setting

(Display example not shown.) This lets you set a low voltage threshold for the unit. If the power input voltage goes down to the level set on this display screen, the RLC-1080 switches to Internal Battery power. The input voltage when this happens can be set from 90 to 100 volts.

OUTLET DELAY1 and

OUTLET DELAY2 Setting

(Only the Outlet Delay1 display screen is shown) This lets you set the amount of time that elapses

(from 0 to 10 seconds) before the RLC-1080 provides power to the rear panel outlets marked Delayed1 (TUNER/AUX) and Delayed2 (SUBWOOFER and/or AMPLIFIER). By setting this delay, it prevents power on or power off glitches from effecting other equipment con- nected to the unit.

������������������

������������������

LOWBATTWARNING: XMIN Setting

This lets you set the unit to sound an alarm when the RLC-1080 is running on battery power and available power from the Battery Pack drops to or below the setting (2 to 25 minutes). For example, if this warning is set to three minutes, and the RLC-1080 is running on battery power, the alarm sounds when the power remaining in the Battery Pack can power the system for only three more minutes. This gives you time to turn off the components of the system before the Battery Pack is depleted.

������������������

������������������

BATREPDATE: XX/XX/XX Setting

This lets you store the exact date a replacement Battery Pack is installed in the unit. After using the Setup button to access this screen, use the Up/Down Arrow buttons to set the correct month, then press the SETUP push button to move the cursor to the day of the month field. Set the day of the month using the Up/Down Arrow buttons. Press the SETUP button again to move the cursor to the year field, then set the year using the Up/Down Arrow buttons.

�������������������

������������������

DO QUIK SELFTEST Screen

This lets you manually initiate a self-test to see that the battery pack is in good condition and that the unit is operating properly. Note: Once you advance to this screen, press either Up/Down Arrow buttons to start the Selftest. During the Selftest the same screens described in the System Test section of this manual are displayed.

�������������������

������������������

Page 11
Image 11
Rotel RLC-1080 Display Dimmer Setting, LED Dimmer Setting, GO to Battery if Xxxv Setting, Lowbattwarning Xmin Setting