Samsung AR24KQJSBWKNMG manual Preparation, Choosing the installation location

Models: AR24KQJSBWKNMG

1 52
Download 52 pages 1.01 Kb
Page 34
Image 34

Preparation

Step 1.1 Choosing the installation location

Overview of installation location requirements

 

 

100 mm or more

125 mm

 

125 mm

or more

 

or more

 

 

 

Drain hose hole

You can select the direction of

draining (left or right).

Maximum pipe height: 15 m

Maximum pipe length: 30 m

Make at least one round to reduce noise and vibration.

The actual units may look different from the images depicted here.

 

 

 

 

 

 

 

(Unit : m)

 

 

 

 

 

 

 

 

 

 

Model

 

Pipe length

Pipe height

 

 

 

 

 

 

 

 

 

Minimum

Maximum

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

✴✴18✴✴

 

3

15

7

 

 

 

 

 

 

 

 

 

✴✴24✴✴

 

3

20

8

 

 

 

 

 

 

 

 

 

Outdoor

 

 

 

 

Make a U-trap (A) on the

Unit

 

 

 

 

pipe (which is connected to

 

 

 

 

 

CAUTION the indoor unit) at outer wall

 

 

 

 

 

Outer wall

 

 

 

 

and cut the bottom part of

Indoor

 

 

 

 

the insulation (about 10 mm)

 

 

 

 

to prevent rainwater from

 

 

 

 

Unit

 

 

 

 

getting inside through the

 

 

 

 

 

 

Cut insulation to have

insulation.

 

 

 

 

 

rainwater drained

 

 

 

 

CAUTION

Comply with the length and height limits described in the figure above.

Minimum clearances for the outdoor unit

Wall

Minimum clearance in mm

300

600

Air flow direction

 

 

Top view

Side view

 

 

When installing 1 outdoor unit

 

(6 cases)

 

 

 

 

 

(Unit: mm)

 

 

 

300

 

1500

 

300

 

 

2000

1500

 

 

150

600

 

 

 

500

300

 

 

300

 

 

 

 

Installation

 

 

 

 

1500

English 33

MG_GOOD_R-410A_A3050_IB&IM_EN_ DB68-06070A-00.indd 33

12-May-16 11:29:33 AM

Page 34
Image 34
Samsung AR24KQJSBWKNMG Preparation, Choosing the installation location, Overview of installation location requirements