Output Connection
DC +12V GND
Door Lock
NC
POWER FAIL SAFE
COM
COM
NO
Alarm Device
GND
POWER FAIL SECURE
- If the door lock is in POWER FAIL SAFE mode: (Door 1: Relay #1, Door 2: Relay #3)
1.Connect the COM line of the Door Lock relay to DC +12V.
2.Connect the plus (+) line of the Door Lock to the Normal Close (NC) line of the Door Lock relay.
3.Connect the minus
- If the Door Lock is in POWER FAIL SECURE mode: (Door 1: Relay #1, Door 2: Relay #3)
1.Connect the COM line of the relay to DC +12V.
2.Connect the plus (+) line of the Door Lock to the Normal Open (NO) line of the Door Lock relay.
3.Connect the minus
Alarm Device Connection (Door 1 Alarm: Relay #2, Door 2 Alarm: Relay #4)
1.Connect the COM line of the alarm device relay to DC +12V.
2.Connect the plus (+) line of the alarm device to the NO line of the alarm device relay.
3.Connect the minus
| Door Number | Door Lock | Alarm Device | Note | |
Two Door Control | 1 | Relay Output #1 | Relay Output #2 |
| |
2 | Relay Output #3 | Relay Output #4 |
| ||
|
| ||||
| 1 | Relay Output #1 | Relay Output #2 |
| |
Three Door Control | 2 | Relay Output #8 | Relay Output #9 | I/O Board | |
| 3 | Relay Output #10 | Relay Output #11 | I/O Board | |
| 1 | Relay Output #1 | Relay Output #2 |
| |
Four Door Control | 2 | Relay Output #3 | Relay Output #4 |
| |
3 | Relay Output #8 | Relay Output #9 | I/O Board | ||
| |||||
| 4 | Relay Output #10 | Relay Output #11 | I/O Board |