Samsung SSA-P401T, SSA-P400T user manual installation and external connection, Termination Resistor

Models: SSA-P400 SSA-P400T SSA-P401T SSA-P401

1 27
Download 27 pages 19.27 Kb
Page 13
Image 13
installation and external connection

installation and external connection

CONNECTING THE TERMINATION RESISTOR AND DIODE

Termination Resistor

A resistor is inserted for matching the line’s impedance to prevent distortion and reduction in RS-422 or RS-485 long distance data communications, which is referred to as termination resistor.

Note that termination resistors of lower than 90 accepted for the communications system.

RS-485/

"

 

RS-485

RS-485

A

 

 

 

 

 

RS-232

 

 

 

 

 

Converter

#

120Ω

Termination Resistors

120Ω

B

 

 

 

 

 

 

 

 

 

 

SSA-P400(401)

<Termination Resistor in RS-485 Communication>

120Ω

TX+

RX+

RS-422/

TX-

RX-

RS-422

RS-422

RS-232

RX+

TX+

Converter

RX-

TX-

 

 

120Ω

SSA-P400(401)

 

Termination Resistors

<Termination Resistor in RS-422 Communication>

INSTALLATION AND EXTERNAL CONNECTION

Bypass Diode Connection

If you connected an inductor (door lock or alarm device) to the output relay, there should occur a voltage surge while the inductor was between turning on and turning off. If you do not connect a bypass diode to the relay, the voltage surge will cause damage to the electric circuit of the controller. To reduce this surge, it is recommended to connect a bypass diode to the relay.

 

DC+

 

DC-

SSA-P400(401)

Lock/Alarm

Cathode Anode

1N4004 ~ 1n4007 or equiv.

13

Page 13
Image 13
Samsung SSA-P401T, SSA-P400T user manual installation and external connection, Connecting The Termination Resistor And Diode