3A. ROUTE CONTROL WIRES TING

3A. ROUTE CONTROL WIRES TING

Install low voltage control wiring from outdoor to indoor unit and from thermostat to indoor unit.

ARun 24VAC control wires through hole with grommet.

BMake 24VAC control wire connections to heat pump control (A175) .

NOTE AC control wires inside control box

.

CONTROL BOX

NOTE

separation of field installed low and high voltage circuits. NOTE .

WIRE RUN LENGTH

AWG# INSULATION TYPE

 

LESS THAN 100’ (30 METERS)

18

TEMPERATURE RATING

MORE THAN 100’ (30 METERS)

16

35ºC MINIMUM.

B

HEAT PUMP CONTROL (A175)

B. ROUTE CONTROL WIRES TING

HOLE A

Maximum length of wiring (18 gauge) for all connections on the RSBus is limited to 1500 feet (457 meters). Color−coded, temperature rating 95ºF (35ºC) minimum, solid core. (Class II Rated Wiring)

4ROUTE HIGH VOLTAGE AND GROUND WIRES

Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.

PIPING PANEL

CONTROL BOX

HIGH VOLTAGE

CONDUIT HOLE

WATERTIGHT

CONDUIT

FITTING

WATERTIGHT

FLEXIBLE

CONDUIT

TO SERVICE

DISCONNECT BOX

GROUND LUG

 

CONTACTOR

ELECTRICAL INLET

(HIGH VOLTAGE)

 

 

WIRING ENTRY POINTS

ELECTRICAL INLET (CONTROL WIRING TAGE).

USE BUSHING PROVIDED IN BAG ASSEMBLY HERE.

ACCESS VIEW

Page 21

XP17 SERIES

Page 21
Image 21
Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS 3A. ROUTE CONTROL WIRES TING, Access View

FAQ

What is the maximum length of wiring for RSBus connections?

The maximum length of wiring for 18 gauge connections on the RSBus is limited to 1500 feet (457 meters).

How should excess high voltage field wiring be handled?

Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring.

What is the recommended temperature rating for the control wires?

The recommended temperature rating for the control wires is 95F (35C) minimum.