Field Configuration and Testing

FAN MOTOR CONTROL (A177) OPERATION, AND

TROUBLESHOOTING

This section provides procedures for configuring,

This section provides information concerning operation

adjusting and testing various components of this unit.

and testing of the fan control.

S Fan Motor (B4) Testi Procedure

Fan Motor Control Sequence of Operation

S Fan Motor Control (A177) Configuration and Testing

During start up, the following sequence is followed:

 

S Top Grille and Fan Motor Mounting Adjustment (Fan

1. Display error conditions (see table 17), if present.

2. If no errors are detected, the LED code indicating

Clearance)

stage operation (see table 18) will display the

 

S Heat Pump Control (A175) Unit Nominal Capacity

applicable code and then a long pause.

Code configuration

3. The fan motor speed / RPM (revolutions per minute)

FAN MOTOR (B4) TEST PROCEDURE

indicator is displayed next (see table 16).

The following procedure can be used to test the fan

4. There is a short pause.

 

motor operation. A fully charged 9V battery will be

The above sequence will continue to repeat if a thermostat

required for this procedure. See figure 31 for complete

demand is present. See figure 32 for LED sequence and

test procedure.

table 18 for description of flash and pause durations.

This is a test that will verify that the motor does operate. 1. Verify main (240 volt) power if OFF to unit.

2. Remove both wires (brown and black) from the J2 terminal on the fan motor control (A177).

3. Room thermostat should be in OFF position (unit in idle mode − no heating or cooling demands)

4. Turn main power (240 volt) ON to unit.

5. Connect 9 Volt battery to fan motor plugs as noted in picture below.

6. Fan motor should run at a reduced fan speed.

7. If fan motor does not run, then replace fan motor assembly.

FAN MOTOR CONTROL

BLACK LEAD

 

 

BROWN LEAD

REMOVE BOTH LEADS FROM J2 TERMINALS

BLACK LEAD

BROWN LEAD

J2

FAN PWM OUT PARK COM

BLACK LEAD

BROWN LEAD

 

CONNECT B4 FAN MOTOR

WIRE TO 9V BATTERY

V POSITIVE TERMINAL

CONNECT B4 FAN

MOTOR BLACK COMMON

WIRE TO 9V BATTERY

NEGATIVE TERMINAL

NEGATIVE TERMINAL

POSITIVE TERMINAL

 

FULLY CHARGED 9V BATTERY

Figure 31. Fan Motor (B4) Test

Page 45

XP17 SERIES

Page 45
Image 45
Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS Field Configuration and Testing