New or Replacement Line Set

New or Replacement Line Set

REFRIGERANT LINE SET

This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 13.

Manual background IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in Table 2, use the procedure outlined under Flushing the System on page 13.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 8 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.

Manual background IMPORTANT

Refrigerant lines must not contact structure.

Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing the System on page 16).

Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.

Table 2. Refrigerant Line Set

 

 

Liquid

Vapor

L15

Model

 

Line Sets

 

Line

Line

 

 

Feet (Meters)

 

 

 

 

 

 

 

 

 

−024 and

 

3/8" (10)

3/4" (19)

L15 line set sizes are depen-

−030

 

 

 

 

dent on unit match up. See

 

 

 

 

 

 

 

 

XP17 Engineering Handbook to

 

 

 

 

−036, −042

 

 

 

determine correct line set sizes.

 

3/8" (10)

7/8" (22)

 

and −048

 

 

 

 

 

 

 

 

 

 

 

−060

 

3/8" (10)

1−1/8"

Field Fabricated

 

(29)

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

1−1/8" adapter

 

 

 

 

 

 

 

 

NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. :

To obtain the correct information from Lennox, be sure to communicate the following information:

SModel (XP17) and size of unit (e.g. −036).

SLine set diameters for the unit being installed as listed in table 2 and total length of installation.

SNumber of elbows vertical rise or drop in the piping.

The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.

Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.

Manual background WARNING

Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.

Manual background IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol ester oil.

Page 11

XP17 SERIES

Page 11
Image 11
Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS, 506586-01 New or Replacement Line Set

FAQ

Why is it important to change the line set when converting from HCFC22 to HFC410A?

Lennox highly recommends changing the line set when converting from HCFC22 to HFC410A due to compatibility and performance reasons.

Can existing line sets be reused when converting the system?

If the existing line set is the proper size and was previously charged with HCFC22 refrigerant, it may be reused if flushed as outlined in the manual.

What type of oil should be added to the system and how much?

For systems over 20 pounds of refrigerant, one ounce of oil should be added for every five pounds of refrigerant. Recommended oils include Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.