System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or defrost/dehumidification).Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.

Heat Pump Control

icomfort

 

 

 

 

LEDs

Touch®

Condition

Possible Cause(s)

 

Solution

 

 

Thermostat

 

DS11

DS14 Red

 

 

 

 

Display

 

 

 

 

Green

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moderate

Discharge line

 

 

 

Slow flash

On

Alert Code

 

 

 

temperature fault

This code indicates high discharge temperatures. If the discharge line temperature

 

 

414

 

 

 

exceeds a temperature of 279ºF (137ºC) during compressor operation, the control

 

 

 

 

 

 

 

Discharge line

will de−energize the compressor contactor output (and the defrost output if active).

 

 

Critical Alert

The compressor will remain off until the discharge temperature has dropped below

Fast flash

On

temperature

Code 415

225ºF (107ºC).

 

 

 

lockout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moderate /

Discharge sensor

The heat pump control (A175) detects open or short sensor or out of temperature

Off

Fast flash

Critical Alert

sensor range. This fault is detected by allowing the unit to run for 90 seconds before

fault

 

 

Code 417

checking sensor resistance. If the sensor resistance is not within range after 90

 

 

 

 

 

 

 

seconds, the control will raise the alarm.

 

 

 

 

 

 

 

 

3 fast

 

Moderate /

W output

When auxiliary heat output is detected as active. Fault in the heat pump control.

flashes

Off

Critical Alert

hardware fault

Replace heat pump control. See figure 30 for further details.

then pause

 

Code 418

 

 

 

 

 

 

 

 

 

 

3 fast

 

Moderate /

W output

If heat pump control recognizes five output hardware fault events during a single

flashes

On

Critical Alert

hardware fault

cooling demand, the heat pump control will initiate a lockout. See figure 30 for fur-

then pause

 

Code 419

lockout

ther details.

 

 

 

 

 

 

 

 

 

3 fast

Critical Alert

W external

When auxiliary heat output is detected as active after compressor has been de−en-

Off

flashes

Code 421

miswire fault

ergized. See figure 30 for further details.

 

 

then pause

 

 

 

 

 

 

 

 

 

 

 

 

Simultaneous fast

None

Second−stage

If the unit is in non−communicating mode and it goes to second stage due to ambi-

heat lock−in

ent temperature being below second stage lock−in setting (E48).

flashes then pause

 

 

 

 

 

 

 

 

 

 

 

 

 

Fast simultaneous flashing of DS11,

OEM mode

Factory test mode.

 

DS13, DS14 and DS15

 

 

 

 

 

 

 

 

 

 

 

1.Pause duration is two (2) seconds.

2.Fast flash duration is 1/2 second. Slow flash duration is one (1) second.

Page 42

506586−01 10/10

Page 42
Image 42
Lennox International Inc 506586-01, Dave Lennox Signature Collection XP17 System HEAT PUMPS Heat Pump Control

FAQ

What do the LED codes indicate?

The LED fault and lockout alarm codes take precedence over system status LED codes, showing the latest active fault or lockout code. If no fault or lockout codes are active, then system status LEDs are displayed.

What causes the temperature fault code 414?

Code 414 indicates high discharge temperatures during compressor operation. If the discharge line temperature exceeds 279F (137C), the compressor contactor output and active defrost output will be deenergized.

How can I address the hardware fault code 418?

The hardware fault code 418 indicates a fault in the heat pump control when auxiliary heat output is detected as active. The recommended solution is to replace the heat pump control.