Field Control Wiring

Field Control Wiring

 

 

Air Hander Control

ComfortSense[ 7000 Thermostats

 

One−Stage

 

 

Catalog # Y0349 or Y2081

 

 

 

 

 

 

Heat Pump Control

 

DS

 

 

 

W

 

O

R

 

 

 

 

On−board link

 

 

 

5

G

 

 

 

 

 

L

 

 

 

 

 

 

 

Low voltage thermostat

 

 

 

 

W2

 

 

6

L

wiring

 

Y2

 

 

Flat metal jumper

 

 

 

 

 

 

H

W1

 

 

 

 

 

 

Y1

 

DH

O

 

 

 

 

 

 

 

 

 

 

 

O

 

 

L

 

 

 

 

 

 

 

DS

 

R

H

 

 

 

 

 

 

2

C

 

C

D

 

 

 

 

 

 

 

Y1

B

 

 

 

 

 

 

 

 

 

Y2

Y2

 

 

i−

 

 

 

 

 

 

 

 

 

i+

 

G

Y1

1

 

 

 

 

 

 

 

 

W3

C

 

 

R

 

 

 

 

 

3

W2

T

 

 

 

 

4

 

 

 

 

 

 

 

 

 

W1

T

 

 

 

 

 

 

1.Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional).

2.R to L connection is required for this model when using the ComfortSense® 7000 − catalog number Y0349 only. Resistor Kit (catalog number 47W97) required and ordered separately.

3.Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For one−stage electric heat, do not remove factory installed metal jumpers.

4.Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For two−stage electric heat, remove factory installed metal jumper between W1 to W2. Then connect thermostat wire between the air handler control’s W2 and the thermostat’s W2 terminal.

5.Cut on−board link (clippable wire) from R−O HEAT PUMP for heat pump applications.

6.Cut on−board link (clippable wire) DS−R for Humiditrol® or Harmony IIIt applications. This will slow the indoor blower motor to the lowest speed setting. See air handler installation instruction or engineering handbook for lowest fan speed information.

Figure 17. ComfortSense® 7000 Series Thermostat Air Hander/One−Stage Heat Pump

Page 25

XP17 SERIES

Page 25
Image 25
Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS, 506586-01 Field Control Wiring, Page

FAQ

What is the outdoor sensor input used for?

Thermostat T terminals are used for outdoor sensor input. It can be used for optional outdoor temperature display on the thermostat.

Is the resistor kit required for ComfortSense 7000 catalog number Y0349?

Yes, R to L connection is required for this model when using the ComfortSense 7000 catalog number Y0349. A Resistor Kit catalog number 47W97 is required and ordered separately.

How should the metal jumpers across W1, W2, and W3 be handled for one-stage electric heat?

The air handler control ships from the factory with metal jumpers installed across W1, W2, and W3. For one-stage electric heat, do not remove the factory-installed metal jumpers.