Recovering Refrigerant from Existing System

Recovering Refrigerant from Existing System

1DISCONNECT POWER

Disconnect all power to the existing outdoor unit at the disconnect switch or main fuse box/breaker panel.

SERVICE DISCONNECT

SWITCH

2CONNECT MANIFOLD GAUGE SET

Connect a gauge set, clean recovery cylinder and a recovery machine to the service ports of the existing unit. Use the instruction provided with the recovery machine to make the connections.

MANIFOLD GAUGES

RECOVERY MACHINE

LOW

HIGH

RECOVERING REFRIGERANT

Remove existing HCFC−22 refrigerant using one of the following methods

CLEAN RECOVERY

OUTDOOR UNIT

3below:

CYLINDER

 

IMPORTANT

 

r

long line sets.

 

 

 

 

 

METHOD 1:

Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.

Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.

METHOD 2:

Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.

The following devices could prevent full system charge recovery into the outdoor unit:

S

S

Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.

Compressor can stop pumping due to tripped internal pressure relief valve.

SCompressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)

Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.

Perform the following task:

AStart the existing HCFC−22 system in the cooling mode and close the liquid line valve.

BUse the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full (high pressure switch will trip and shut the compressor off). Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refriger- ant from the system.

NOTE

CWhen the low side system pressures reach 0 psig, close the vapor line valve.

DCheck gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.

Figure 3. Refrigerant Recovery Procedure

Page 6

506586−01 10/10

Page 6
Image 6
Lennox International Inc 506586-01 installation instructions Recovering Refrigerant from Existing System, long line sets

FAQ

What are the steps to recover refrigerant from an existing system?

The steps include disconnecting power, connecting a manifold gauge set and recovery machine, and using one of the two recommended methods to remove the existing refrigerant.

When should I use method 1 for refrigerant recovery?

Use method 1 if the existing outdoor unit is not equipped with shutoff valves, or if the unit is not operational and you plan to use the existing HCFC22 to flush the system.

What precautions should I take when using method 2 for refrigerant recovery?

When using method 2, be aware of the potential system conditions that could prevent full system charge recovery into the outdoor unit, and follow the specific instructions for shutting off the vapor valve and using a recovery machine.