Air Handler / Coil Match ups and Targeted Subcooling Values

Listed below are the targeted subcooling and charging values for approved indoor unit air handler / coil match ups. This information is also listed on the unit charging sticker located on the access panel.

*Indicates amount of charge required in additional to charge shown on unit nameplate. Remember to consider line set length differences.

Table 4. XP17−024

 

Target

*Add

INDOOR MATCHUPS

Subcooling

charge

Heat

Cool

 

 

 

lb

oz

 

(+5ºF)

 

 

1ºF)

 

 

 

 

 

CBX27UH−024

16

3

1

6

 

 

 

 

 

CBX27UH−030

16

5

1

9

 

 

 

 

 

CBX32M−030

16

3

1

6

 

 

 

 

 

CBX32M−036

16

5

1

9

 

 

 

 

 

CBX32MV−024/030

16

3

1

6

 

 

 

 

 

CBX32MV−036

16

5

1

9

 

 

 

 

 

CBX40UHV−024, −030, −036

16

5

1

9

 

 

 

 

 

CH23−51

16

3

1

6

 

 

 

 

 

CH33−31

16

3

0

11

 

 

 

 

 

CH33−42

16

3

0

11

 

 

 

 

 

CR33−48

28

3

0

0

 

 

 

 

 

CX34−31

16

3

1

6

 

 

 

 

 

CX34−38

16

5

1

9

 

 

 

 

 

 

 

Table 5. XP17−030

 

Target

*Add

INDOOR MATCHUPS

Subcooling

charge

Heat

Cool

 

 

 

lb

oz

 

(+5ºF)

 

 

1ºF)

 

 

 

 

 

CBX27UH−030, −036

15

5

1

3

 

 

 

 

 

CBX32M−030

19

5

1

7

 

 

 

 

 

CBX32M−036

15

5

1

3

 

 

 

 

 

CBX32MV−024/030

19

5

1

7

 

 

 

 

 

CBX32MV−036

15

5

1

3

 

 

 

 

 

CBX40UHV−024, −030, −036

15

5

1

3

 

 

 

 

 

CH23−51

19

5

1

7

 

 

 

 

 

CH33−31

19

5

1

7

 

 

 

 

 

CH33−42

19

5

1

7

 

 

 

 

 

CR33−48

30

4

0

0

 

 

 

 

 

CX34−31

19

5

1

7

 

 

 

 

 

CX34−38

15

5

1

3

 

 

 

 

 

CX34−43

6

4

0

11

 

 

 

 

 

CX34−44/48B

15

5

1

3

 

 

 

 

 

CX34−49

8

8

1

14

 

 

 

 

 

CX34−50/60C

6

4

0

11

 

 

 

 

 

 

 

Table 6. XP17−036

 

Target

*Add

INDOOR MATCHUPS

Subcooling

charge

Heat

Cool

 

 

 

lb

oz

 

(+5ºF)

 

 

1ºF)

 

 

 

 

 

CBX27UH−036

19

7

1

1

 

 

 

 

 

CBX27UH−042

12

5

2

4

 

 

 

 

 

CBX32M−036, −042

19

7

1

1

 

 

 

 

 

CBX32M−048

12

5

2

4

 

 

 

 

 

CBX32MV−036

19

7

1

1

 

 

 

 

 

CBX32MV−048

12

5

2

4

 

 

 

 

 

CBX40UHV−036

19

7

1

1

 

 

 

 

 

CBX40UHV−042, −048

12

5

2

4

 

 

 

 

 

CH23−51

19

7

0

10

 

 

 

 

 

CH33−42, −43

18

6

1

4

 

 

 

 

 

CH33−44/48B

18

6

1

4

 

 

 

 

 

CH33−48C

18

6

1

4

 

 

 

 

 

CR33−48

32

4

0

0

 

 

 

 

 

CX34−38

19

7

1

1

 

 

 

 

 

CX34−43

18

6

1

4

 

 

 

 

 

CX34−44/48B

19

7

1

1

 

 

 

 

 

CX34−49

9

9

2

8

 

 

 

 

 

CX34−50/60C

18

6

1

4

 

 

 

 

 

 

 

Table 7. XP17−042

 

Target

*Add

INDOOR MATCHUPS

Subcooling

charge

Heat

Cool

 

 

 

lb

oz

 

(+5ºF)

 

 

1ºF)

 

 

 

 

 

CBX27UH−042, −048

12

4

1

0

 

 

 

 

 

CBX32M−048

12

4

1

0

 

 

 

 

 

CBX32MV−048

12

4

1

0

 

 

 

 

 

CBX40UHV−042, −048

12

4

1

0

 

 

 

 

 

CH23−51

17

7

0

0

 

 

 

 

 

CH33−43

14

4

0

0

 

 

 

 

 

CH33−44/48B, −48C, −49C

14

4

0

0

 

 

 

 

 

CH33−50/60C

14

4

0

0

 

 

 

 

 

CR33−48

36

4

0

0

 

 

 

 

 

CR33−50/60

11

6

0

8

 

 

 

 

 

CX34−38

19

6

0

6

 

 

 

 

 

CX34−43

14

4

0

0

 

 

 

 

 

CX34−44/48B

19

6

0

6

 

 

 

 

 

CX34−49

8

7

1

0

 

 

 

 

 

CX34−50/60C

14

4

0

0

 

 

 

 

 

 

 

Table 8. XP17−048

 

Target

*Add

INDOOR MATCHUPS

Subcooling

charge

Heat

Cool

 

 

 

lb

oz

 

(+5ºF)

 

 

1ºF)

 

 

 

 

 

CBX27UH−048

23

3

0

2

 

 

 

 

 

CBX27UH−060

15

8

2

8

 

 

 

 

 

CBX32M−048

23

3

0

2

 

 

 

 

 

CBX32M−060

20

5

1

0

 

 

 

 

 

CBX32MV−048

23

3

0

2

 

 

 

 

 

CBX32MV−060

20

5

1

0

 

 

 

 

 

CBX32MV−068

15

5

1

7

 

 

 

 

 

CBX40UHV−048

23

3

0

2

 

 

 

 

 

CBX40UHV−060

20

5

1

0

 

 

 

 

 

CH23−68

15

8

2

8

 

 

 

 

 

CH33−49C

20

5

1

0

 

 

 

 

 

CH33−50/60C

20

5

1

0

 

 

 

 

 

CH33−60D

25

4

0

0

 

 

 

 

 

CH33−62D

15

5

1

7

 

 

 

 

 

CR33−50/60, −60D

21

4

0

0

 

 

 

 

 

CX34−49

15

6

1

0

 

 

 

 

 

CX34−60D

25

4

0

0

 

 

 

 

 

CX34−62C, −62D

11

4

1

5

 

 

 

 

 

 

 

Table 9. XP17−060

 

Target

*Add

INDOOR MATCHUPS

Subcooling

charge

Heat

Cool

 

 

 

lb

oz

 

(+5ºF)

 

 

1ºF)

 

 

 

 

 

CBX27UH−048

14

3

0

0

 

 

 

 

 

CBX27UH−060

15

8

1

8

 

 

 

 

 

CBX32M−048

14

3

0

0

 

 

 

 

 

CBX32M−060

16

3

0

12

 

 

 

 

 

CBX32MV−048

14

3

0

0

 

 

 

 

 

CBX32MV−060

16

3

0

12

 

 

 

 

 

CBX32MV−068

13

5

0

15

 

 

 

 

 

CBX40UHV−048

14

3

0

0

 

 

 

 

 

CBX40UHV−060

16

3

0

12

 

 

 

 

 

CH23−68

18

8

1

8

 

 

 

 

 

CH33−49C

16

3

0

12

 

 

 

 

 

CH33−50/60C

16

3

0

12

 

 

 

 

 

CH33−62D

13

5

0

15

 

 

 

 

 

CR33−50/60, −60D

21

4

0

0

 

 

 

 

 

CX34−49

16

3

0

12

 

 

 

 

 

CX34−60D

13

5

0

15

 

 

 

 

 

CX34−62C, −62D

13

5

0

15

 

 

 

 

 

 

 

Page 30

506586−01 10/10

Page 30
Image 30
Lennox International Inc 506586-01 installation instructions Air Handler / Coil Match ups and Targeted Subcooling Values