Y1 DEMAND

LOW

 

PRESSURE

CLOSED

SWITCH (S87)

 

COMPRESSOR CONTACTOR ENERGIZED

INITIAL TRIP

SWITCH IS

IGNORED FOR 90 SECONDS

OPEN

OPEN

COMPRESSOR CONTACTOR DE−ENERGIZED

COMPRESSOR ANTI−SHORT CYCLE TIMER BEGINS

INCREMENT

5−STRIKE

COUNTER1

LED ALERT

CODE / OR

MODERATE

ALERT 410

DISPLAYED

ANTI−SHORT CYCLE TIMER ENDS

COMPRESSOR CONTACTOR ENERGIZED

LOW

 

 

 

 

SWITCH IS CLOSED OR OUTDOOR

PRESSURE

 

 

 

 

 

CLOSED

 

 

SWITCH (S87)

 

 

 

AMBIENT TEMPERATURE IS 15ºF

 

 

 

 

 

 

 

 

 

OR BELOW

 

 

 

 

 

 

1If 5−strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will reset to zero. In a icomfort Touch® thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.

2Lockouts can be reset by either cycling power off to the heat pump con- trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) between 1 to 2 seconds.

5−STRIKE

COUNTER

REACHES 5

WITHIN A SINGLE

Y1 DEMAND

LOW

PRESSURE

SWITCH (S87)

LOCKOUT

LED ALERT

CODE / OR

SERVICE

CRITICALREQUIRED2

ALERT 411

DISPLAYED

SERVICE

REQUIRED2

OPEN

LOW

PRESSURE SWITCH (S87)

WAITING FOR PRESSURE SWITCH TO CLOSE

LED ALERT

CODE / OR

CLOSEDMODERATE ALERT 410

DISPLAYED

CLOSED

NORMAL

OPERATION

Figure 28. Low Pressure (S87) Switch Operation

Page 36