Y1 DEMAND

HIGH

 

PRESSURE

CLOSED

SWITCH (S4)

 

COMPRESSOR CONTACTOR ENERGIZED

OPEN

Manual background OPEN

COMPRESSOR CONTACTOR DE−ENERGIZED

COMPRESSOR ANTI−SHORT CYCLE TIMER BEGINS

INCREMENT

5−STRIKE

COUNTER1

LED ALERT

CODE / OR

MODERATE

ALERT 412

DISPLAYED

ANTI−SHORT CYCLE TIMER ENDS

COMPRESSOR CONTACTOR ENERGIZED

HIGH

PRESSURECLOSED

SWITCH (S4)

1If 5−strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will reset to zero. In a icomfort Touch® thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.

2Lockouts can be reset by either cycling power off to the heat pump con- trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) be- tween 1 to 2 seconds.

5−STRIKE

COUNTER

REACHES 5

WITHIN A SINGLE

Y1 DEMAND

HIGH

PRESSURE

SWITCH (S4)

LOCKOUT

LED ALERT

 

CODE / OR

SERVICE

CRITICAL

REQUIRED2

ALERT 413

 

CLEARED

 

SERVICE

REQUIRED2

OPEN

HIGH

PRESSURE SWITCH (S4)

WAITING FOR PRESSURE SWITCH TO CLOSE

LED ALERT

CODE / OR

CLOSED Manual background MODERATE ALERT 412 DISPLAYED

CLOSED

NORMAL

OPERATION

Figure 29. High Pressure Switch (S4) Sequence of Operation

Page 37

XP17 SERIES

Page 37
Image 37
Lennox International Inc Dave Lennox Signature Collection XP17 System HEAT PUMPS, 506586-01 installation instructions Page

FAQ

What happens if the 5strike counter reaches 5 during a single Y1 demand?

If the 5strike counter reaches 5 within a single Y1 demand, the high pressure switch S4 will go into lockout mode. Check LED alert code or service required.

How can lockouts be reset?

Lockouts can be reset by either cycling power off to the heat pump controls A175 R terminal, or placing a jumper on the field test pins E33 between 1 to 2 seconds.

What should be done if a moderate alert 412 is displayed?

If a moderate alert 412 is displayed, the high pressure switch S4 may be closed. Check the pressure and wait for the switch to close for normal operation.