Y1 DEMAND

HIGH

 

PRESSURE

CLOSED

SWITCH (S4)

 

COMPRESSOR CONTACTOR ENERGIZED

OPEN

OPEN

COMPRESSOR CONTACTOR DE−ENERGIZED

COMPRESSOR ANTI−SHORT CYCLE TIMER BEGINS

INCREMENT

5−STRIKE

COUNTER1

LED ALERT

CODE / OR

MODERATE

ALERT 412

DISPLAYED

ANTI−SHORT CYCLE TIMER ENDS

COMPRESSOR CONTACTOR ENERGIZED

HIGH

PRESSURECLOSED

SWITCH (S4)

1If 5−strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will reset to zero. In a icomfort Touch® thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.

2Lockouts can be reset by either cycling power off to the heat pump con- trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) be- tween 1 to 2 seconds.

5−STRIKE

COUNTER

REACHES 5

WITHIN A SINGLE

Y1 DEMAND

HIGH

PRESSURE

SWITCH (S4)

LOCKOUT

LED ALERT

 

CODE / OR

SERVICE

CRITICAL

REQUIRED2

ALERT 413

 

CLEARED

 

SERVICE

REQUIRED2

OPEN

HIGH

PRESSURE SWITCH (S4)

WAITING FOR PRESSURE SWITCH TO CLOSE

LED ALERT

CODE / OR

CLOSED MODERATE ALERT 412 DISPLAYED

CLOSED

NORMAL

OPERATION

Figure 29. High Pressure Switch (S4) Sequence of Operation

Page 37

XP17 SERIES

Page 37
Image 37