Lennox International Inc 506586-01 installation instructions W Input Fault or Miswire Page

Models: Dave Lennox Signature Collection XP17 System HEAT PUMPS 506586-01

1 54
Download 54 pages 9.7 Kb
Page 38
Image 38
Figure 30. W Input Fault or Miswire

Y1 DEMAND

COMPRESSOR CONTACTOR ENERGIZED

Manual background YES

COMPRESSOR CONTACTOR DE−ENERGIZED

INITIAL TRIP

SWITCH IS

IGNORED FOR 90 SECONDS

W OUTPUT

NO

ACTIVE)

 

NORMAL

OPERATION

WOUTPUT ACTIVE)

NO

COMPRESSOR ANTI−SHORT CYCLE TIMER BEGINS

INCREMENT

5−STRIKE

COUNTER1

LED ALERT CODE / OR MODERATE ALERT 418 DISPLAYED

 

 

 

COMPRESSOR

 

 

 

ANTI−SHORT

YES

 

 

 

 

CYCLE TIMER

 

 

 

 

 

 

BEGINS

 

 

 

 

5−STRIKE

COUNTER

REACHES 5

WITHIN A SINGLE

Y1 DEMAND

WOUTPUT HARDWARE

FAULT

LOCKOUT

LED ALERT

CODE / OR

MODERATE

ALERT 418

DISPLAYED

ANTI−SHORT

CYCLE TIMER

ENDS

W OUTPUT

NO

ACTIVE)

 

YES

WAITING FOR

W OUTPUT TO

DEACTIVATE

LED ALERT CODE / OR MODERATE ALERT 418 CLEARED

ANTI−SHORT CYCLE TIMER ENDS

LED ALERT CODE / OR MODERATE ALERT 418 CLEARED

LED ALERT

 

CODE / OR

SERVICE

CRITICAL

REQUIRED2

ALERT 419

 

DISPLAYED

 

1If 5−strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will reset to zero. In a icomfort Touch® thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.

2Lockouts can be reset by either cycling power off to the heat pump control’s (A175) R terminal, or placing a jumper on the field test pins (E33) between 1 to 2 seconds.

Figure 30. W Input Fault or Miswire

Page 38

506586−01 10/10

Page 38
Image 38
Lennox International Inc 506586-01, Dave Lennox Signature Collection XP17 System HEAT PUMPS W Input Fault or Miswire Page

FAQ

How to reset lockouts?

Lockouts can be reset by either cycling power off to the heat pump controls A175 R terminal, or placing a jumper on the field test pins E33 between 1 to 2 seconds.

What to do if LED alert code 418 is displayed?

If LED alert code 418 is displayed, it indicates a hardware fault or lockout. Follow the instructions on the manual to clear the alert code.

When will the 5-strike counter reset?

If 5-strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will reset to zero. In a icomfort Touch thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is deenergized.