Lennox International Inc 506586-01 1PIPING PANEL REMOVAL AND PREPARING LINE SET

Models: Dave Lennox Signature Collection XP17 System HEAT PUMPS 506586-01

1 54
Download 54 pages 9.7 Kb
Page 14
Image 14
1PIPING PANEL REMOVAL AND PREPARING LINE

1PIPING PANEL REMOVAL AND PREPARING LINE

SET

Remove piping panel for easier access to service valves. Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.

CUT AND DEBUR

LINE SET SIZE MATCHES

SERVICE VALVE CONNECTION

SERVICE VALVE

CONNECTION

COPPER TUBE

STUB

REDUCER

LINE SET SIZE IS SMALLER

THAN CONNECTION

REFRIGERANT LINE

DO NOT CRIMP SERVICE VALVE

CONNECTOR WHEN PIPE IS

SMALLER THAN CONNECTION

2CAP AND CORE REMOVAL

Remove service cap and core from both the suction / vapor and liquid line service ports.

SERVICE PORT CAP

SERVICE PORT

CORE

LIQUID LINE SERVICE VALVE

SERVICE PORT

CORE

SERVICE

PORT CAP

SUCTION / VAPOR LINE

SERVICE VALVE

3ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES

AConnect gauge set low pressure side to liquid line service valve (service port).

BConnect gauge set center port to bottle of nitrogen with regulator.

CWith valve core removed from the suction / vapor line service port, nitrogen flow will have an exit point.

SUCTION / VAPOR SERVICE PORT MUST BE OPEN AND SERVICE PORT CORE REMOVED

TO ALLOW EXIT POINT FOR NITROGEN FLOW C

SUCTION / VAPOR

LINE

INDOOR

UNIT

LOW

ATTACH

GAUGES

SUCTION /

VAPOR LINE

SERVICE

VALVE

HIGH

B

OUTDOOR

UNIT

NITROGEN

LIQUID LINE

LIQUID LINE SERVICE

A

VALVE

 

 

Figure 9. Brazing Procedures

Page 14

506586−01 10/10

Page 14
Image 14
Lennox International Inc 506586-01 1PIPING PANEL REMOVAL AND PREPARING LINE SET, 2CAP AND CORE REMOVAL

FAQ

How do I remove the piping panel?

To remove the piping panel, simply follow the steps outlined in the article, ensuring that the pipe remains round and free from nicks or dents.

What is the procedure for cap and core removal?

The procedure for cap and core removal from the suction/vapor and liquid line service ports is detailed in the article, providing a comprehensive guide.

How to attach the manifold gauge set for brazing?

Follow the step-by-step instructions in the article to attach the manifold gauge set for brazing liquid and suction/vapor line service valves.