INSTALLING THE INDOOR UNIT

Cutting/Extending the Piping

Five metres(16ft 5in) of piping is supplied with the air conditioner(Optional). This length can if necessary be:

Extended to a maximum of “L” m/ft.

Shortened as required

If more than 5m(16ft 5in) of piping is required:

The assembly cable must also be extended

Refrigerant must be added to the circuit by an approved installer; otherwise, the indoor unit may freeze

1Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder).

2If you wish to shorten the piping, cut it using a pipe cutter, taking care to

ensure that the cut edge remains at a 90° angle with the side of the pipe, and referring to the illustrations below for examples of edges cut correctly and incorrectly.

90O

Oblique

Rough

Burr

O

x

x

x

3 To prevent any gas from leaking out, remove all burrs at the cut end of the pipe, using a reamer.

4Slide a flare nut on to the pipe and modify the flare.

Pipe

Outer Diameter (D)

Depth (A)

Liquid refrigerant

6.35 mm(1/4˝)

1.3 mm(1/16˝)

Gas refrigerant

9.52 mm(3/8˝)

1.8 mm(1/16˝)

Gas refrigerant

12.70 mm(1/2˝)

2.0 mm(1/16˝)

Gas refrigerant

15.88 mm(5/8˝)

2.2 mm(1/8˝)

5Check that the flaring is correct, referring to the illustrations below for examples of incorrect flaring.

Inclined

Damaged Surface

Cracked

Uneven Thickness

6 Align the pipes to be connected and tighten the flare nuts first manually and then with a wrench, applying the following torque.

Pipe

Outer Diameter

Torque

Liquid refrigerant

6.35 mm(1/4˝)

160kg•cm(11.6ft•lb )

Gas refrigerant

9.52 mm(3/8˝)

300kg•cm(21.8ft•lb )

Gas refrigerant

12.70 mm(1/2˝)

500kg•cm(36.4ft•lb )

Gas refrigerant

15.88 mm(5/8˝)

700kg•cm(50.6ft•lb )

7For further details on how to connect up to the outdoor unit and purge the circuit, refer to page 41.